Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
Signal Ports
10 V
3
D.C Power
Ports
10 V
3
AC Power
Ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
ground Ports
10 V
3
IEC
61000-4-8
Magnetic Field
Enclosure
Ports
40 A/m continuous,
1000 A/m for 1 s
DC Power
Ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC
61000-4-29
30% for 1 period,
60% for 50 periods
IEC
61000-4-11
Voltage Dips and Interrupts
AC Power
Ports
100% for 5 periods,
100% for 50 periods
Signal Ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
DC Power
Ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
AC Power
Ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
Signal Ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-16
Mains Frequency Voltage
DC Power
Ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply
DC Power
Ports
10%
3
Signal Ports
2 kVAC (Fail-
Safe Relay output)
DC Power
Ports
2 kV
Dielectric Strength
AC Power
Ports
2 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
DC Power
Ports
5 kV
IEC 60255-5
HV Impulse
AC Power
Ports
5 kV
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
The RUGGEDCOM RS940G meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
RUGGEDCOM RS940G
Installation Manual, 01/2021, C79000-G8976-1036-07
35