Optical channel
Permitted FO cable attenuation (with link power margin)
– with plastic fiber 980/1000
– with PCF fiber 200/230
13 dB
3 dB
Link distance with 3 dB link power margin
– with plastic fiber 980/1000 with max. 200 dB/km cable
attenuation
– with PCF fiber 200/230 with max. 10 dB/km cable attenua-
tion
0.1 m to 50 m
0 m to 300 m
Fiberoptic connectors
Simplex / duplex
Electromagnetic compatibility (EMC)
Emission
Limit class A (EN 55022)
Immunity against static discharge
On shield connector and housing parts: ±6 kV contact dis-
charge (IEC 61000-4-2)
Immunity against RF radiation
10 V/m at 80% amplitude modulation with 1 kHz, 80 MHz –
1 GHz (ENV 50140; IEC 61000–4–3)
10 V/m with 50% load factor at 900 MHz (to ENV 50 204)
10 V/m at 80% amplitude modulation with 1 kHz, 10kHz –
80 MHz (ENV 50141)
Immunity to conducted disturbances (burst)
On power supply cables and shielded RS-485 bus cables:
±2 kV
(IEC 61000–4–4)
Immunity to conducted disturbances (surge)
On power supply cables: ±1 kV symmetrical and +-2 KV
asymmetrical
On shielded RS485 bus cables: ±2 kV asymmetrical
(IEC 61000–4-5)
Safety
VDE regulation
VDE 0806 = EN60950 and IEC 60950-1
UL/CSA approval
complying with UL 60950-1, CSA C22.2 No. 60950-00
Climatic environmental conditions
Ambient temperature
0 °C to +60 °C
(IEC 60068-2-1, IEC 60068-2-2)
Storage temperature
-40 °C to +70 °C
(IEC 60068-2-1, IEC 60068-2-2)