Dealing with Problems / Error Displays
6-3
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
6.2
Error Displays of the CP 243-2 / Remedying Errors
<F 1>The following table lists the possible causes of errors that can occur when
operating the CP 243-2 and how to remedy the problem.
Table 6-1
Error Displays of the CP 243-2 / Remedying Errors
Error
Possible Cause
Remedy
APF LED lit
The AS-Interface power supply
unit is not connected or is defec-
tive.
Check the connection of the AS-
Interface power supply unit; if ne-
cessary replace the power supply
unit.
Power requirements of the AS-In-
terface slaves are too high. Re-
sult: The voltage on the AS-Inter-
face cable is too low.
Check the power requirements of
the AS-Interface slaves. If neces-
sary, supply the slaves with power
externally.
Short-circuit on the AS-Interface
cable.
Check the AS-Interface cable and
the attached slaves.
SF lights up without pressing the
SET button.
The CP 243-2 is defective. Inter-
nal EEPROM error.
Replace the CP 243-2.
SF is lit when the SET button is
pressed.
An AS-Interface slave with ad-
dress 0 exists when there is a
change to the protected mode.
Remove the slave with address 0
from the AS-Interface cable.
CER is lit permanently.
The CP 243-2 has not yet been
configured.
Configure the CP 243-2 using the
mode button on the front panel.
A configured AS-Interface slave
has failed (evaluate the slave dis-
play).
Replace the defective AS-Inter-
face slave or configure the
CP 243-2 again if the slave is not
required.
An unconfigured AS-Interface
slave was connected to the AS-In-
terface cable.
Remove the AS-Interface slave or
reconfigure the CP 243-2 .
An AS-Interface slave was con-
nected whose configuration data
(I/O configuration, ID codes) do
not match the values of the confi-
gured AS-Interface slave.
Check whether the wrong AS-In-
terface slave has been connec-
ted. If necessary, reconfigure the
CP 243-2.
CER display flickers, in other
words a configured AS-Interface
slave is lost sporadically.
Bad electrical connection.
Check the electrical connections
of the AS-Interface slaves.
Noise affecting the AS-Interface
cable.
Check the correct grounding of
the S7-200 and check the AS-In-
terface cable. Check that the
shield of the AS-Interface power
supply unit is connected correctly.
Содержание SIMATIC NET CP 243-2
Страница 4: ...Preface ii SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Страница 8: ...Contents vi SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Страница 26: ...Technical Description and Installation Instructions 1 18 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Страница 64: ...Access to the Data of the AS i Slaves 3 16 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Страница 68: ...Signaling Errors and Diagnostics in the User Program 4 4 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Страница 128: ...Command Interface 5 60 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Страница 134: ...Dealing with Problems Error Displays 6 6 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Страница 142: ...Notes on the CE Mark C 2 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Страница 148: ...Glossary Glossary 4 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...