Description of the device
1.2 CP 1616 communications processor
CP 1604 / CP 1616
Operating Instructions, 02/2017, C70000-G8976-C218-08
21
Properties
The CP 1616 is a PCI module for connecting PGs/PCs to Industrial Ethernet. The essential
properties are as follows:
●
Optimized for PROFINET IO
●
With Ethernet realtime ASIC ERTEC 400
●
Four RJ-45 jacks for connection of end devices or other network components
●
Integrated 4-port real-time switch
●
Automatic hardware detection is supported
Hardware requirements
To be able to operate, the CP 1616 requires a 32-bit wide, short PCI slot with master
capability.
LED display
On the front of the CP 1616, there are 10 LEDs.
Above the four RJ-45 jacks, there are 2 red LEDs labeled "BF" (bus fault) and "SF" (group
fault).
LEDs in the frame of each RJ-45 jack
Within the frame of each RJ-45 jack, there are 2 LEDs.
The upper green LED is lit when a connection is established (Link LED).
The lower yellow LED is lit when sending and receiving (Activity LED).
BF and SF LED
The BF and SF LEDs have the following significance:
BF LED
SF LED
Description
off
-
Communications connection is established.
on
-
Link status error has occurred.
flashing slowly
-
There are two possible causes:
•
An IO device cannot be addressed.
•
An IP address was assigned twice.
–
off
There are two possible causes:
•
No fault/error.
•
A download is in progress.
on
Diagnostics information is available.
flashing at 2 second in-
tervals
The firmware of the module is in an inconsistent status.
This status is possible, for example if the power supply was inter-
rupted during a firmware update. Eliminate the error as described in
the section "Eliminating problems (Page 84)".
alternating slow flashing
Flash test for module detection.