Start-up
SIMATIC MV230
Operating Instructions, 01/2007 Edition, A5E00749101-01
19
t
cyc
Cycle time
max. 50 ms
t
trg
Trigger pulse
width
min. 1 ms
Smaller pulse widths are not
detected by the sensor as a trig-
ger.
t
delay
Response time
max. 16 ms
t
proc
Processing time
max. 34 ms
Image evaluation and capture
t
out
Output
signal
15 ms
External:
The output signal is reset with a
new trigger pulse. The signal
remains on for at least 15 ms.
Free Run:
At the end of the last test (and
TRG = 0), the result is still present
for 15 ms.