Wiring
4-39
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
6. If required, make the following settings:
Setting the output voltage
The output voltage can be set in the range from 22.8 V to 25.2 V using
potentiometer R306.
AC 120V
AC 120/230V
50/60Hz
L+ M
OUTPUT
AD-
JUST
INPUT
24 VDC / 10A
22.8...25.2
VDC
N L1
L+ M
LINK
R306
Figure 4-23
Potentiometer R306 for setting the output voltage
!
Warning
Potentiometer R306 may only be operated with an insulated screwdriver in
accordance with DIN 7437, because components carrying dangerous electrical
voltage may be touched unintentionally.