Compatibility
6.1 Compatibility of modules
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
50
Manual, 10/2018, A5E03915895-AH
Required tools
3 to 3.5 mm screwdriver (for resetting via the RESET button)
Procedure
1.
Remove the interface module from the mounting rail and swivel it downwards.
2.
The RESET button is located on the back of the interface module behind a small opening:
Push a screwdriver into the small opening, thus pressing the RESET button.
3.
Release the RESET button.
4.
Press the RESET button for another 3 seconds.
5.
Look at the LED display of the interface module to see whether the reset was successful:
RUN LED flashes for 3 seconds, ERROR and MAINT LED are off.
6.
Install the interface module back on the mounting rail.
7.
Assign parameters to the interface module again.
AQ 4xU/I ST analog output module
Note
For operation of the AQ 4xU/I ST analog output module, firmware version V1.0 (6ES7135-
6HD00-0BA1) with the interface module, you need to set the "Reaction to CPU STOP"
parameter to "Turn off" with a PROFINET send clock < 1 ms.
Reaction times for fail-safe modules
The following maximum reaction time of the interface module must be taken into account
when calculating the reaction times of fail-safe modules: Maximum reaction time =
configured update time + 400 μs (but at least 1.4 ms)
Operation with activated system redundancy S2
Note
Restrictions in operation with activated system redundancy S2
You cannot use the following functions during operation of the IM155-6 PN/2 HF, firmware
version V4.2 with activated system redundancy S2:
•
Configuration control (option handling)
•
Module-to-Module Communication (MtM)