Compatibility
6.1 Compatibility of modules
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
Manual, 10/2018, A5E03915895-AH
49
The table below shows all modules that do not support a station configuration with more than
32 I/O modules:
Table 6- 1
Incompatible modules with functional status
Modules
Article number
Up to functional status
Analog modules
AI 4xI 2-/4-wire ST
6ES7134-6GD00-0BA1
002
AI 4xU/I 2-wire ST
6ES7134-6HD00-0BA1
002
AI 4xRTD/TC 2-/3-/4-wire HF
6ES7134-6JD00-0CA1
002
AI 4xU/I ST
6ES7135-6HD00-0BA1
002
Digital modules
DI 16x24VDC ST
6ES7131-6BH00-0BA0
002
DI 8x24VDC ST
6ES7131-6BF00-0BA0
002
DQ 16x24VDC/0.5A ST
6ES7132-6BH00-0BA0
002
DQ 4x24VDC/2A ST
6ES7132-6BD20-0BA0
002
DQ 8x24VDC/0.5A ST
6ES7132-6BF00-0BA0
002
Status of the supply voltage
Load voltage diagnostics are only valid if the station started up with a valid and complete
configuration.
●
For modules without parameter assignment in the following table, the status of the supply
voltage (status byte of the server module) is always signaled as "1" regardless of the
actual status of the supply voltage.
●
If a potential group is exclusively made up of modules without parameter assignment from
the table below, no group diagnostics "Missing supply voltage L+" is signaled for this
potential group.
Modules
Article number
DI 8x24VDC ST
6ES7131-6BF00-0BA0
DI 16x24VDC ST
6ES7131-6BH00-0BA0
DI 8x24VDC HF
6ES7131-6BF00-0CA0
DQ 4x24VDC/2A ST
6ES7132-6BD20-0BA0
DQ 8x24VDC/0.5A ST
6ES7132-6BF00-0BA0
DQ 16x24VDC/0.5A ST
6ES7132-6BH00-0BA0
DQ 8x24VDC/0.5A HF
6ES7132-6BF00-0CA0
Resetting an interface module to factory settings via the RESET button
There is a special operation for interface module IM 155-6 PN/2 HF to reset it to the factory
settings using the Reset button.
Requirements
The supply voltage to the interface module must be switched on.
Содержание SIMATIC ET 200SP IM 155-6 PN/2 HF
Страница 1: ......