8-10
ET 200L Distributed I/O Device
EWA-4NEB 780600902-05
The following table shows the technical data of the L 32 DI DC 24 V elec-
tronics block.
Dimensions and Weight
Dimensions
W
H
D (mm)
145
60
60.5
Weight
Approx. 150 g
Module-Specific Data
Baud rate
9.6; 19.2; 45,45*; 93.75;
187.5; 500 and
1500 kBaud
Bus protocol
PROFIBUS-DP
FREEZE compatibility
Yes
Number of inputs
32
Cable length
S
Unshielded
Max. 600 m
S
Shielded
Max. 1000 m
Manufacturer ID
0015
H
Voltages, Currents, Potentials
Rated supply voltage for
electronics (4L+, 5L+)
24 V DC
S
Reverse polarity
protection
Yes
S
Power failure with-
stand time
At least 20 ms
Rated load voltage
(1L+, 2L+ and 3L+)
24 V DC
Maximum number of in-
puts driven simultaneously
32
Galvanic isolation
S
Between channels
No
S
Between channels and
PROFIBUS-DP
Yes
Insulation tested with
500 V DC
Power input
S
from supply voltage
L4+/L5+
Max. 70 mA
S
from load voltage L1+
and L2+/L3+ (without
load)
Max. 100 mA per load
group
Power loss of module
Typically 3.2 W
Status, Interrupts, Diagnostics
Status display
Green LED per channel
Interrupts
None
Diagnostic function
Yes
S
Bus monitoring PRO-
FIBUS-DP
Red ”BF” LED
S
Monitoring of elec-
tronics power supply
Green ”ON” LED
Sensor Selection Data
Input voltage
S
Rated value
24 V DC
S
At signal ”1”
13 to 30 V
S
At signal ”0”
-30 to 5 V
Input current
S
At signal ”1”
Typically 5 mA at 24 V
Input delay
S
With ”0” after ”1”
2.0 to 4.5 ms
S
With ”1” after ”0”
2.0 to 4.5 ms
Input characteristic
To IEC 1131-2 Type 1
Connection of 2-wire
BEROs
Possible
S
Permissible closed-cir-
cuit current
Max. 1.5 mA
*
If you want to run the ET 200L, ET 200L–SC or ET 200L–SC IM–SC at a transmission rate of 45.45 kbps, you
must use an updated device master file or STEP 7 as of 4.02 (K4.02.6).
Technical Data
ET 200L Electronics Blocks – Technical Data