Definition
Identification data represent information stored on the module and support you in:
●
Troubleshooting a plant
●
Verifying your plant configuration
●
Locating hardware modifications in a plant
This ID data allows the unambiguous identification of modules in online mode. As of order
no. 6ES7 340–1xH02–0AE0, this data is available on the CP 340.
To view the identification data, select PLC > Module Information , or Read Data Record (see
below).
Reading the identification data
Users can access specific ID data by selecting Read Data Record.
The element of the ID data which is assigned to the corresponding index is found under the
associated data record number.
All data records which contain ID data have a length of 64 bytes.
The table below shows the structure of those data records.
Table 5- 2
Data record structure
Content
Length (bytes)
Coding (hex)
Header information
SZL ID
2
F1 11
Index
2
00 0x
Length of identification data
2
00 38
Number of blocks which contain ID data
2
00 01
Table 5- 3
Identification data
Identification data
Index
2
00 0x
Identification data associated with the relevant
index
54
Содержание SIMATIC CP 340
Страница 6: ...Preface PtP coupling and configuration of CP 340 6 Manual 04 2011 A5E00369892 03 ...
Страница 10: ...Table of contents PtP coupling and configuration of CP 340 10 Manual 04 2011 A5E00369892 03 ...
Страница 186: ...Accessories and Order Numbers PtP coupling and configuration of CP 340 186 Manual 04 2011 A5E00369892 03 ...
Страница 190: ...Literature on SIMATIC S7 PtP coupling and configuration of CP 340 190 Manual 04 2011 A5E00369892 03 ...
Страница 200: ...Index PtP coupling and configuration of CP 340 200 Manual 04 2011 A5E00369892 03 ...