Diagnostics with the CP 340
8.2 Diagnostics Messages of the Function Blocks P_SEND, P_RCV and P_PRINT
PtP coupling and configuration of CP 340
136
Manual, 04/2011, A5E00369892-03
Event class 5 (05H):
"Error while processing CPU request"
Event no.
Event
To correct or avoid errors
(05)1BH
Only for printer drivers:
Precision invalid
Correct the specified precision in the conversion
statement. The precision is always initialized with a
dot prefix to identify and limit the width (for example,
".2" to output the decimal point and two decimals.)
Precision is only relevant to display types A, D, F,
and R. It is ignored otherwise.
(05)1CH
Only for printer drivers:
Variable invalid
(variable length incorrect/incorrect type)
Correct the specified variable. The corresponding
table indicates the possible data types for each
display type.
(05)1EH
Only for printer drivers:
The "line end sequences" sent with this job (i.e.:
$R / $L / $N) do not fit (any longer) on the (initial)
page.
Increase the length of your page, reduce the number
of lines (or line feeds) or spread your printout over a
number of pages.
Event class 7 (07H):
"Send error"
Event no.
Event
To correct or avoid errors
(07)01H
Only for 3964(R):
Sending of the first repetition:
An error was detected when transmitting the
telegram, or
The partner requested a repetition by means of
a negative acknowledgment character (NAK).
A repetition is not an error, but it can indicate that
there is interference on the data link or the partner
device has malfunctioned. If the telegram still has
not been transmitted after the maximum number of
repetitions, an error number is output that describes
the first error that occurred.
(07)02H
Only for 3964(R):
Error establishing connection:
After STX was sent, NAK or any other code
(except for DLE or STX) was received.
Check for malfunction of the partner device; you may
need to use an interface test device (FOXPG)
interconnected in the data link.
(07)03H
Only for 3964(R):
Acknowledgment delay time (QVZ) exceeded:
After STX was sent, partner did not respond within
the acknowledgment delay time.
The partner device is too slow or not ready to
receive, or there is a break in the transmission line,
for example. Check for malfunction of the partner
device; you may need to use an interface test device
(FOXPG) interconnected in the data link.
(07)04H
Only for 3964(R):
Termination by partner:
One or more codes were received from the partner
during sending.
Check whether the partner is also indicating errors,
possibly because not all transmitted data arrived
(e.g., break in the transmission line), fatal errors are
pending or the partner device has malfunctioned.
You may need to use an interface test device
(FOXPG) interconnected in the data link to check
this.
Содержание SIMATIC CP 340
Страница 6: ...Preface PtP coupling and configuration of CP 340 6 Manual 04 2011 A5E00369892 03 ...
Страница 10: ...Table of contents PtP coupling and configuration of CP 340 10 Manual 04 2011 A5E00369892 03 ...
Страница 186: ...Accessories and Order Numbers PtP coupling and configuration of CP 340 186 Manual 04 2011 A5E00369892 03 ...
Страница 190: ...Literature on SIMATIC S7 PtP coupling and configuration of CP 340 190 Manual 04 2011 A5E00369892 03 ...
Страница 200: ...Index PtP coupling and configuration of CP 340 200 Manual 04 2011 A5E00369892 03 ...