Power modules
ET 200S
Manual, Edition 10/2005, A5E00514527-01
2-11
Block diagram
01
3
3
)6*
3:5
9'&/
%
D
F
N
S
OD
Q
HE
X
V
(76
EDFNSODQH
EXV
FLUFXLW
)XVH
PRQLWRULQJ
/RDG
YROWDJH
PRQLWRULQJ
)XVHV
Figure 2-5
Block diagram of the PM-E 24-48 VDC, 24-230 VAC
PM-E 24 VDC to 48 VDC/24 VAC to 230 VAC technical specifications (6ES7138-4CB10-0AB0)
Dimensions and Weight
Dimensions W × H × D (mm)
(the total dimensions depend on the selected
terminal module)
15 × 81 × 52
Weight
34 g
Voltages, currents, potentials
Rated load voltage
24 VDC to 56.7 VDC
24 VAC to 48 VAC/120 VAC/230 VAC
•
Overvoltage protection
Yes
Protection with automatic circuit breakers
yes, tripping characteristic B, C
Max. current-carrying capacity
10 A
•
For 24-56.7 VDC
up to 30 °C: max. 10 A
up to 40 °C: max. 9 A
up to 60 °C: max. 7 A
•
For 24-48/120/230 VAC
up to 30 °C: max. 8 A
up to 40 °C: max. 7 A
up to 60 °C: max. 5 A
•
Short-circuit protection
yes, IEC 127-2/1, 250 V, 10 A,
fast fuse (5 x 20 mm), replaceable
1
Galvanic isolation
•
Between rated load voltage and backplane
bus
•
Between the power modules
Yes
Yes
Insulation test voltage
1500 VAC
Current consumption from backplane bus
max. 9.5 mA
Содержание Simantic ET 200S
Страница 8: ...Table of contents ET 200S viii Manual Edition 10 2005 A5E00514527 01 ...
Страница 242: ......
Страница 270: ...Glossary ET 200S Glossary 10 Manual Edition 10 2005 A5E00514527 01 ...