Analog electronic modules
4.2 Analog value representation
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-9
Measuring ranges for resistance thermometer Cu 10 Climatic
Table 4-13 SIMATIC S7 format: Measuring ranges Cu 10 Climatic in °C and °F
Units
Units
Cu 10 Climatic in °C
(1 digit = 0.01 °C)
Decimal Hexadecima
l
Cu 10 Climatic in °F
(1 digit = 0.01° F)
Decimal
Hexadeci
mal
Range
> 180.00
32767
7FFF
H
> 325.11
32767
7FFF
H
Overflow
180.00
:
150.01
18000
:
15001
H
:
3A99
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61A
H
Overshoot range
150.00
:
-50.00
15000
:
-5000
3A98
H
:
EC78
H
280.00
:
-58.00
28000
:
-5800
6D60
H
:
E958
H
Rated range
-50.01
:
-60.00
-5001
:
-6000
EC77
H
:
E890
H
-58.01
:
-76.00
-5801
:
-7600
E957
H
:
E250
H
Undershoot
range
< -60.00
-32768
8000
H
< -76.00
-32768
8000
H
Underflow
4.2.5
Measuring Range of the Analog Input Modules in SIMATIC S7 Format for
Thermocouples
Measuring range for thermocouple: Type B
Table 4-14 SIMATIC S7 format: Measuring range Type B in °C and °F
Units
Units
Type B in °C
Decimal Hexadecima
l
Type B in °F
Decimal
Hexadeci
mal
Range
> 2070.0
32767
7FFF
H
> 3276.6
32767
7FFF
H
Overflow
2070.0
:
1820.1
20700
:
18201
50DC
H
:
4719
H
3276.6
:
2786.6
32766
:
27866
7FFE
H
:
6CDA
H
Overshoot range
1820.0
:
0.0
18200
:
0
4718
H
:
0000
H
2786.5
:
32
27865
:
320
6CD9
H
:
0140
H
Rated range
-0.1
:
-120.0
-1
:
-1200
FFFF
H
:
FB50
H
31.9
:
-184.0
319
:
-1840
013F
H
:
F8D0
H
Undershoot
range
< -120.0
-32768
8000
H
< -184.0
-32768
8000
H
Underflow
Содержание Simantic ET 200S
Страница 8: ...Table of contents ET 200S viii Manual Edition 10 2005 A5E00514527 01 ...
Страница 242: ......
Страница 270: ...Glossary ET 200S Glossary 10 Manual Edition 10 2005 A5E00514527 01 ...