Analog electronic modules
4.19 2AO U Standard analog electronic module (6ES7135-4FB01-0AB0)
ET 200S
4-98
Manual, Edition 10/2005, A5E00514527-01
Status, interrupts, diagnostics
Diagnostics function
•
Group error
Red "SF" LED
•
Diagnostic functions readable
Yes
Analog value generation
Resolution (including overrange)
± 10 V/13 bits + sign
1 to 5 V/12 bits
Cycle time
max. 1.5 ms
Settling time
•
For resistive load
0.1 ms
•
For capacitive load
0.5 ms
•
For inductive load
0.5 ms
Substitute value can be assigned parameters Yes
Suppression of interference, limits of error
Crosstalk between the outputs
min. -40 dB
Operational limit (in the entire temperature
range, with reference to the output range)
± 0.4 %
Basic error limit (operational limit at 25 °C with
reference to output range)
± 0.2 %
Temperature error (with reference to the
output range)
± 0.01 %/K
Linearity error (with reference to the output
range)
± 0.02 %
Repeatability
(in steady state at 25 °C with reference to
output range)
± 0.05 %
Output ripple (with reference to output range,
bandwidth 0 to 50 kHz)
± 0.02 %
Data for selecting an actuator
Output range (rated value)
± 10 V
1 V to 5 V
Load resistance
min. 1.0 kΩ
•
For capacitive load
max. 1 µF
•
Short-circuit protection
Yes
•
Short-circuit voltage
Approx. 25 mA
Destruction limit against voltages/currents
applied from outside
•
Voltage at the outputs to M
ANA
15 V continuous; 75 V for max. 1 ms
(sampling ratio 1:20)
•
Current
max. 50 mA DC
Connection of actuators
•
Two-wire connection
Possible, without compensation of cable resistance
•
Four-wire connection
Yes
Содержание Simantic ET 200S