4.3.4 Transferring data sets
If extremely large quantities of data are to be transferred, e.g. for
visualization applications (WinCC), or if data have to be transferred
between SIMATIC and FM 458 for an extremely high number of drives.
•
Memory available on the P bus: 114688 bytes (0x1C000 hex), for
various "data sets" (or "telegrams").
•
max. 125 read and 125 write data sets
•
max. length per data set (telegram): 240 bytes
•
max. data quantity which can be transferred:
For internal data management and buffer mechanisms, the following
are required
- for received data sets, 2x data set length
- for sent data sets 3x data set length
The sum of the required bytes for all of the write and read data sets
may not exceed the above mentioned memory size of 114688 bytes!
Example:
Max. number of write and read data sets, each 240 bytes:
114688 bytes / (5 * 240 bytes) = 95.5733
A maximum of 95 write- and 95 read data sets, each with 240 bytes can
be configured.
“
S
ystem
F
unction
C
alls” SFC are used in the SIMATIC-CPU for data set
transfer:
•
write
SFC 58
data set (to the FM 458)
•
read
SFC 59
to the data set (from FM 458)
This coupling type is configured on the FM 458 in 3 steps:
1. Establish the coupling:
Configure a central communications block
@CPB
(from the
“SpezKomm” block family) to initialize and monitor the data set
coupling.
2. Define the send and receive data sets:
A function block must be configured for each data set (telegram):
CRV
to receive,
CTV
to send
Data/entries at the CRV/CTV connections:
−
CTS = FM458.
P_B
Connection is connected to the P bus coupling:
Application
Features,
limit values
SIMATIC S7
access with SFC
FM 458 with “virtual
connections”
Содержание SIMADYN D FM 458
Страница 2: ...http www bzxindaxin com http www gk world com 全球独家推出 全覆盖型省配线解决方案 ...
Страница 3: ...http www bzxindaxin com http www gk world com ...
Страница 4: ...http www bzxindaxin com http www gk world com ...
Страница 5: ...http www bzxindaxin com http www gk world com ...
Страница 6: ......
Страница 11: ...Definitions 1 2 Application Module FM 458 User Manual 6DD1904 0AE0 Edition 12 2001 ...
Страница 123: ...ESD guidelines 5 4 Application Module FM 458 User Manual 6DD1904 0AE0 Edition 12 2001 ...