Siemens SIDS-T40026-00-4AUS Скачать руководство пользователя страница 6

Description and control

Description and control

The SIERS electrical racking system is 
powered by 125 Vdc or (optionally) by  
120 Vac power from the controller. Typically, 
ac power is obtained from a control power 
transformer (CPT) in the controller, or from 
the user’s external source. However, power 
from the controller CPT is not available 
when the equipment is de-energized. For 
this reason, it is preferred that a dc source 
(125 Vdc) be used to power the SIERS 
electrical racking system, as this power will 
normally be available even when the 
equipment itself is de-energized. Control 
power requirements are detailed in Table 1.

In the event a dc source is not available and 
ac power is not available, the isolating 
switch can be operated manually, following 
the normal procedures given in the relevant 
instruction manual.

If control power is provided from a 
controller CPT, the wiring to the power 
supply for the racking system will be 
installed in the controller at the factory. 

Option: external ac supply for 
maintenance

If 120 Vac control power is obtained from a 
remote source, such as a wall outlet in the 
vicinity of the controller or from a portable 
generator, the control power connection 
should be made to the control power socket 
installed in the controller as shown in Figure 
2: Flanged inlet type 5-15P (on right) for 
connection to external 120 Vac power 
source extension cord receptacle type 5-15R 
(on left). The receptacle (socket with male 
pins) is a NEMA standard type 5-15P 
recessed socket (referred to as a flanged 
inlet in NEMA standard WD6) for use with a 
NEMA standard 5-15R female receptacle, 
three wire with ground.

The SIERS electrical racking system controls 
are located in a self-contained enclosure on 
the top of each controller section (Figure 4: 
Control devices for SIERS racking system).

The SIERS electrical racking system circuit 
includes miniature circuit breaker protection 
for both the 125 Vdc and 120 Vac supplies (if 
applicable), and fuse protection for the 
motor (FU2) supply circuit and the 24 Vdc 
power supply circuit (FU1), as well as for the 
24 Vdc supply (FU3) to the current switch, 
logic module, and digital module. 

The fuse in the motor circuit has time-delay 
characteristics to avoid fuse operation on 
motor inrush current.

The SIERS system is controlled using a 
Siemens LOGO! programmable logic module 
(LM) with digital expansion module (DM) 
with auxiliary relays for motor control. The 
LM receives input from limit switches on the 
racking mechanism that signal the isolating 
switch position (OPEN/DISCONNECT or 
CLOSE/CONNECT). The limit switches also 
illuminate the light-emitting diode (LED) 
pushbuttons on the control pendant, which 
indicate the isolating switch position. A solid 
green LED indicates OPEN/DISCONNECT 
position and solid red LED indicates CLOSE/
CONNECT position. 

A blinking LED indicates the position 
towards which the isolating switch is 
moving.

The LM responds to commands from the 
pushbuttons on the control pendant to 
move the isolating switch between 
positions.

The system includes current sensing to 
respond to excessive current in the motor 
circuit. Excessive current indicates a motor 
overload, whether due to a jam or 
otherwise. When the overcurrent is 
detected, the LM initiates alarm indication 
on the amber LED on the hand-held control 
pendant, and stops the racking process. 
After a time period of five seconds, the LM 
restarts the racking process to move the 
isolating switch to OPEN/DISCONNECT 
position. 

If this is unsuccessful, a second attempt to 
rack to the OPEN/DISCONNECT position is 
initiated after a time period of five seconds. 
If the second attempt is also unsuccessful, 
the LM disables electrical function, and the 
user must use the manual procedure to 
operate the isolating switch to the OPEN/
DISCONNECT position. 

Figure 2: Flanged inlet type 5-15P 

(on right) for connection to 

external 120 Vac power source 

extension cord receptacle type 

5-15R (on left) (optional)

Voltage

I (nominal) A

I (maximum) A

Racking time s

125 Vdc

0.9

1.6

< 2

120 Vac

0.9

1.6

< 2

Table 1: Control power requirements

6

SIERS Siemens Integrated Electrical Racking System | 

Instruction manual

Содержание SIDS-T40026-00-4AUS

Страница 1: ...a siemens com simovac SIDS T40026 00 4AUS SIERS Siemens integrated electrical racking system instruction manual for SIMOVAC non arc resistant and SIMOVAC AR arc resistant medium voltage motor controllers ...

Страница 2: ...ms from contact with energized electrical conductors or circuit parts Further a qualified person shall also be familiar with the proper use of special precautionary techniques personal protective equipment insulation and shielding materials and insulated tools and test equipment Such persons are permitted to work within limited approach boundary and shall at a minimum be additionally trained in al...

Страница 3: ...onnection with installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the local sales office The contents of this instruction manual shall not become part of or modify any prior or existing agreement commitment or relationship The sales contract c...

Страница 4: ...equipment Maintenance should be performed only by qualified personnel The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions which will cause death severe injury or equipment damage Follow all safety instructions contained herein Read understand and follow all of the safety advisories instructions and procedures contai...

Страница 5: ... or serious injury Warning Indicates a potentially hazardous situation that if not avoided could result in death or serious injury Caution Indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury Notice Indicates a potentially hazardous situation that if not avoided may result in property damage Field service operation and warranty issues Siemens can p...

Страница 6: ...nd fuse protection for the motor FU2 supply circuit and the 24 Vdc power supply circuit FU1 as well as for the 24 Vdc supply FU3 to the current switch logic module and digital module The fuse in the motor circuit has time delay characteristics to avoid fuse operation on motor inrush current The SIERS system is controlled using a Siemens LOGO programmable logic module LM with digital expansion modu...

Страница 7: ...nt of the controller using a 9 pin connector Hand held remote control control pendant The hand held control pendant includes three illuminated LED pushbuttons red CLOSE CONNECT green OPEN DISCONNECT and white TEST plus an amber LED used for alarm purposes The amber alarm LED illuminates to indicate an alarm condition such as a fault alarm obstruction overcurrent or excessive time elapsed when movi...

Страница 8: ...ally by means of a HMI or PLC through SCADA system 2 Normally open contact to sense door position If the controller high voltage compartment door is open the LM blocks power to the racking motor The compartment door must be closed to enable electrical racking 3 Normally open contact on the lever access mechanism assembly to disable electrical racking when the manual lever is inserted This permissi...

Страница 9: ...e pendant also includes an amber light for error or malfunction indication Control using hand held control pendant Control using communications system and discrete I O Discrete I O control optional allows the user to operate the SIERS racking system via a PLC or protection relay input output signals These systems can be wired to a central control room or to a remote panel located away from the con...

Страница 10: ...n used for moving the slider up and provides access to the lever 2 Lever access 2 1 Figure 7 Mechanical and electrical interlock for manual operation 10 SIERS Siemens Integrated Electrical Racking System Instruction manual ...

Страница 11: ... switch reaches the CLOSE CONNECT position 3 Once the isolating switch reaches the CLOSE CONNECT position the red LED for CLOSE CONNECT position will illuminate 4 With the isolating switch in CLOSE CONNECT position it is possible to close and open the contactor 5 To proceed to move the isolating switch to OPEN DISCONNECT position verify that the contactor is OPEN and the manual lever is dismounted...

Страница 12: ... five seconds and try the racking process again Motor time out If the racking process takes more time that the system allows SIERS stops the racking process Once the issue is found and corrected close and securely latch the compartment door and try the racking process again Open permissive switch This error is caused by an open contact in one of the protection permissive switches One permissive sw...

Страница 13: ...cking system 2 Follow the normal procedures contained in the applicable SIMOVAC non arc resistant and SIMOVAC AR arc resistant medium voltage motor controller instruction manual use the manual lever to move the isolating switch into the desired position Manual racking 13 Instruction manual SIERS Siemens Integrated Electrical Racking System ...

Страница 14: ...14 SIERS Siemens Integrated Electrical Racking System Instruction manual ...

Страница 15: ...15 Instruction manual SIERS Siemens Integrated Electrical Racking System ...

Страница 16: ...tual case or on as designed parameters and therefore should not be relied upon for any specific application and does not constitute a performance guarantee for any projects Actual results are dependent on variable conditions Accordingly Siemens does not make representations warranties or assurances as to the accuracy currency or completeness of the content contained herein If requested we will pro...

Отзывы: