Alarms and troubleshooting 

The SIERS electrical racking system includes 
alarm functions to indicate unusual 
conditions as indicated by an amber LED on 
the hand-held control pendant. If control of 
the SIERS system is through the user’s 
communication system, an alarm indication 
is provided through the communications 
channel. 

The alarm is actuated for any of the 
following conditions:

• 

  Motor overcurrent

 

When the overcurrent is detected, the 
LM initiates alarm indication on the 
amber LED on the control pendant, and 
stops the racking process. After a time 
period of five seconds, the LM restarts 
the racking process to move the 
isolating switch to the OPEN/
DISCONNECT position. If this is 
unsuccessful, a second attempt to rack 
to the OPEN/DISCONNECT position is 
initiated after a time period of five 
seconds. If the second attempt is also 
unsuccessful, the LM disables electrical 
racking, and the user must use the 
manual lever to move the isolating 
switch to OPEN/DISCONNECT position. 

         If the amber alarm LED is illuminated, 

use the manual lever to move the 
isolating switch to the OPEN/
DISCONNECT position. 

         Verify that the isolating switch is in the 

OPEN/DISCONNECT position. Unlatch 
and open the compartment door. 
Inspect the isolating switch and the 
racking system, levers, chain, and 
control system in the compartment to 
determine the source of the problem. 

         Once the issue is found and corrected, 

close and securely latch the 
compartment door, reset the alarm by 
pressing the OPEN/DISCONNECT 
pushbutton for five seconds and try the 
racking process again.

• 

Motor time out

 

If the racking process takes more time 
that the system allows, SIERS stops the 
racking process. 

         Once the issue is found and corrected,  

close and securely latch the 
compartment door, and try the racking 
process again.

• 

Open permissive switch

 

This error is caused by an open contact 
in one of the protection permissive 
switches. One permissive switch is for 
insertion of the manual lever. The 
second permissive switch is for an open 
compartment door. The third permissive 
switch is for sensing contactor status, 
which must be open to allow racking.

        Check that all three permissive switches 

are in the correct positions, that the 
contactor is open, that the 
compartment door is closed, and the 
manual lever is not inserted. Then try 
the racking process again.

• 

Isolating switch position “unknown”

 

If none of the indicating lights on the 
hand-held control pendant are 
illuminated, and there is control power 
available, it means that the isolating 
switch is not in a defined position.

        Verify that the contactor is in the OPEN 

position and with the manual lever 
move the isolating switch to the OPEN/
DISCONNECT position. Open the high-
voltage compartment door. Inspect the 
racking system, lever, chain, and control 
system in the compartment to 
determine the source of the problem. 
Once the issue is found and corrected, 
close and latch the high-voltage 
compartment door. Then, use the 
manual operation method to switch the 
isolating switch to the desired position.

Alarms and troubleshooting

Note: If none of these 
troubleshooting actions 
resolves the issue, contact 
Siemens for assistance.

12

SIERS Siemens Integrated Electrical Racking System | 

Instruction manual

12

Содержание SIDS-T40026-00-4AUS

Страница 1: ...a siemens com simovac SIDS T40026 00 4AUS SIERS Siemens integrated electrical racking system instruction manual for SIMOVAC non arc resistant and SIMOVAC AR arc resistant medium voltage motor controllers ...

Страница 2: ...ms from contact with energized electrical conductors or circuit parts Further a qualified person shall also be familiar with the proper use of special precautionary techniques personal protective equipment insulation and shielding materials and insulated tools and test equipment Such persons are permitted to work within limited approach boundary and shall at a minimum be additionally trained in al...

Страница 3: ...onnection with installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the local sales office The contents of this instruction manual shall not become part of or modify any prior or existing agreement commitment or relationship The sales contract c...

Страница 4: ...equipment Maintenance should be performed only by qualified personnel The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions which will cause death severe injury or equipment damage Follow all safety instructions contained herein Read understand and follow all of the safety advisories instructions and procedures contai...

Страница 5: ... or serious injury Warning Indicates a potentially hazardous situation that if not avoided could result in death or serious injury Caution Indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury Notice Indicates a potentially hazardous situation that if not avoided may result in property damage Field service operation and warranty issues Siemens can p...

Страница 6: ...nd fuse protection for the motor FU2 supply circuit and the 24 Vdc power supply circuit FU1 as well as for the 24 Vdc supply FU3 to the current switch logic module and digital module The fuse in the motor circuit has time delay characteristics to avoid fuse operation on motor inrush current The SIERS system is controlled using a Siemens LOGO programmable logic module LM with digital expansion modu...

Страница 7: ...nt of the controller using a 9 pin connector Hand held remote control control pendant The hand held control pendant includes three illuminated LED pushbuttons red CLOSE CONNECT green OPEN DISCONNECT and white TEST plus an amber LED used for alarm purposes The amber alarm LED illuminates to indicate an alarm condition such as a fault alarm obstruction overcurrent or excessive time elapsed when movi...

Страница 8: ...ally by means of a HMI or PLC through SCADA system 2 Normally open contact to sense door position If the controller high voltage compartment door is open the LM blocks power to the racking motor The compartment door must be closed to enable electrical racking 3 Normally open contact on the lever access mechanism assembly to disable electrical racking when the manual lever is inserted This permissi...

Страница 9: ...e pendant also includes an amber light for error or malfunction indication Control using hand held control pendant Control using communications system and discrete I O Discrete I O control optional allows the user to operate the SIERS racking system via a PLC or protection relay input output signals These systems can be wired to a central control room or to a remote panel located away from the con...

Страница 10: ...n used for moving the slider up and provides access to the lever 2 Lever access 2 1 Figure 7 Mechanical and electrical interlock for manual operation 10 SIERS Siemens Integrated Electrical Racking System Instruction manual ...

Страница 11: ... switch reaches the CLOSE CONNECT position 3 Once the isolating switch reaches the CLOSE CONNECT position the red LED for CLOSE CONNECT position will illuminate 4 With the isolating switch in CLOSE CONNECT position it is possible to close and open the contactor 5 To proceed to move the isolating switch to OPEN DISCONNECT position verify that the contactor is OPEN and the manual lever is dismounted...

Страница 12: ... five seconds and try the racking process again Motor time out If the racking process takes more time that the system allows SIERS stops the racking process Once the issue is found and corrected close and securely latch the compartment door and try the racking process again Open permissive switch This error is caused by an open contact in one of the protection permissive switches One permissive sw...

Страница 13: ...cking system 2 Follow the normal procedures contained in the applicable SIMOVAC non arc resistant and SIMOVAC AR arc resistant medium voltage motor controller instruction manual use the manual lever to move the isolating switch into the desired position Manual racking 13 Instruction manual SIERS Siemens Integrated Electrical Racking System ...

Страница 14: ...14 SIERS Siemens Integrated Electrical Racking System Instruction manual ...

Страница 15: ...15 Instruction manual SIERS Siemens Integrated Electrical Racking System ...

Страница 16: ...tual case or on as designed parameters and therefore should not be relied upon for any specific application and does not constitute a performance guarantee for any projects Actual results are dependent on variable conditions Accordingly Siemens does not make representations warranties or assurances as to the accuracy currency or completeness of the content contained herein If requested we will pro...

Отзывы: