Operation sequence

The operation sequence that follows 
describes the control using the hand-held 
control pendant. Operation over a 
communication channel is the same except 
for manual cable connection steps.

1.  Connect the hand-held control pendant 

cable plug to the receptacle for the 
appropriate controller compartment. 
With the isolating switch in the OPEN/
DISCONNECT position, the green LED 
will illuminate. Before proceeding to 
switch to the CLOSE/CONNECT position, 
verify the following:

• 

High-voltage compartment door is 
closed and latched.

• 

Contactor is in the OPEN position.

• 

Lever for manual operation has been 
dismounted.

2.  Press the pushbutton for the CLOSE/

CONNECT position. Please note it is not 
necessary to hold the button down. 
When the isolating switch begins to 
move, the green LED (for OPEN/
DISCONNECT position) will turn off and 
the red LED (for CLOSE/CONNECT 
position) will start to blink until the 
isolating switch reaches the CLOSE/
CONNECT position. 

3.  Once the isolating switch reaches the 

CLOSE/CONNECT position, the red LED 
(for CLOSE/CONNECT position) will 
illuminate. 

4.  With the isolating switch in CLOSE/

CONNECT position, it is possible to 
close and open the contactor.

5.  To proceed to move the isolating 

switch to OPEN/DISCONNECT position, 
verify that the contactor is OPEN and 
the manual lever is dismounted. 

6.  Press the pushbutton for the OPEN/

DISCONNECT position. Please note it is 
not necessary to hold the button 
down. When the isolating switch 
begins to move, the red LED (for 
CLOSE/CONNECT position) will turn off 
and the green LED (for OPEN/
DISCONNECT position) will start to 
blink until the isolating switch reaches 
the OPEN/DISCONNECT position. 

7.  Once the isolating switch reaches the 

OPEN/DISCONNECT position, the green 
LED (for OPEN/DISCONNECT position) 
will illuminate.

8.  With the isolating switch in the OPEN/

DISCONNECT position, it is possible to 
open or close the contactor, or if 
needed, open the high-voltage 
compartment door.

Operation sequence

Instruction manual

 | SIERS Siemens Integrated Electrical Racking System

Содержание SIDS-T40026-00-4AUS

Страница 1: ...a siemens com simovac SIDS T40026 00 4AUS SIERS Siemens integrated electrical racking system instruction manual for SIMOVAC non arc resistant and SIMOVAC AR arc resistant medium voltage motor controllers ...

Страница 2: ...ms from contact with energized electrical conductors or circuit parts Further a qualified person shall also be familiar with the proper use of special precautionary techniques personal protective equipment insulation and shielding materials and insulated tools and test equipment Such persons are permitted to work within limited approach boundary and shall at a minimum be additionally trained in al...

Страница 3: ...onnection with installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the local sales office The contents of this instruction manual shall not become part of or modify any prior or existing agreement commitment or relationship The sales contract c...

Страница 4: ...equipment Maintenance should be performed only by qualified personnel The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions which will cause death severe injury or equipment damage Follow all safety instructions contained herein Read understand and follow all of the safety advisories instructions and procedures contai...

Страница 5: ... or serious injury Warning Indicates a potentially hazardous situation that if not avoided could result in death or serious injury Caution Indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury Notice Indicates a potentially hazardous situation that if not avoided may result in property damage Field service operation and warranty issues Siemens can p...

Страница 6: ...nd fuse protection for the motor FU2 supply circuit and the 24 Vdc power supply circuit FU1 as well as for the 24 Vdc supply FU3 to the current switch logic module and digital module The fuse in the motor circuit has time delay characteristics to avoid fuse operation on motor inrush current The SIERS system is controlled using a Siemens LOGO programmable logic module LM with digital expansion modu...

Страница 7: ...nt of the controller using a 9 pin connector Hand held remote control control pendant The hand held control pendant includes three illuminated LED pushbuttons red CLOSE CONNECT green OPEN DISCONNECT and white TEST plus an amber LED used for alarm purposes The amber alarm LED illuminates to indicate an alarm condition such as a fault alarm obstruction overcurrent or excessive time elapsed when movi...

Страница 8: ...ally by means of a HMI or PLC through SCADA system 2 Normally open contact to sense door position If the controller high voltage compartment door is open the LM blocks power to the racking motor The compartment door must be closed to enable electrical racking 3 Normally open contact on the lever access mechanism assembly to disable electrical racking when the manual lever is inserted This permissi...

Страница 9: ...e pendant also includes an amber light for error or malfunction indication Control using hand held control pendant Control using communications system and discrete I O Discrete I O control optional allows the user to operate the SIERS racking system via a PLC or protection relay input output signals These systems can be wired to a central control room or to a remote panel located away from the con...

Страница 10: ...n used for moving the slider up and provides access to the lever 2 Lever access 2 1 Figure 7 Mechanical and electrical interlock for manual operation 10 SIERS Siemens Integrated Electrical Racking System Instruction manual ...

Страница 11: ... switch reaches the CLOSE CONNECT position 3 Once the isolating switch reaches the CLOSE CONNECT position the red LED for CLOSE CONNECT position will illuminate 4 With the isolating switch in CLOSE CONNECT position it is possible to close and open the contactor 5 To proceed to move the isolating switch to OPEN DISCONNECT position verify that the contactor is OPEN and the manual lever is dismounted...

Страница 12: ... five seconds and try the racking process again Motor time out If the racking process takes more time that the system allows SIERS stops the racking process Once the issue is found and corrected close and securely latch the compartment door and try the racking process again Open permissive switch This error is caused by an open contact in one of the protection permissive switches One permissive sw...

Страница 13: ...cking system 2 Follow the normal procedures contained in the applicable SIMOVAC non arc resistant and SIMOVAC AR arc resistant medium voltage motor controller instruction manual use the manual lever to move the isolating switch into the desired position Manual racking 13 Instruction manual SIERS Siemens Integrated Electrical Racking System ...

Страница 14: ...14 SIERS Siemens Integrated Electrical Racking System Instruction manual ...

Страница 15: ...15 Instruction manual SIERS Siemens Integrated Electrical Racking System ...

Страница 16: ...tual case or on as designed parameters and therefore should not be relied upon for any specific application and does not constitute a performance guarantee for any projects Actual results are dependent on variable conditions Accordingly Siemens does not make representations warranties or assurances as to the accuracy currency or completeness of the content contained herein If requested we will pro...

Отзывы: