
Communication
6.2.4 Information mapping table
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-
4
, Release Date
06.2018
49
Alarm manner
control byte
0103 H
unsigned int
2 bytes
R/W
0 ... 3
0: turn off alarm function
1: relay output 1 is used
for alarm
2: relay output 2 is used
for alarm
3: output ports 1 and 2
are all used for alarm
Alarm status byte
0106 H
unsigned int
2 bytes
R
0 ... 0x3F
From low to high, each
bit means status of an
alarm group:
0: no alarm activated
1: in alarm status
BO1 Relay oper-
ation time
0107 H
unsigned int
2 bytes
R/W
0 or 100 ...
3000
Unit: ms. Value 0 is for
latched output; value
100~3000 for pulse
output
BO2 Relay oper-
ation time
0109 H
unsigned int
2 bytes
R/W
0 or 100 ...
3000
Unit: ms. Value 0 is for
latched output; value
100~3000 for pulse
output
Alarm 1
Out-of-limit
data type
0110 H
unsigned int
2 bytes
R/W
0 ... 34
See alarm type table
High 16 bits
of out- of-limit
threshold
0111 H
unsigned long
4 bytes
R/W
Arbitrary
value
Threshold=set val-
ue/100
Low 16 bits
of out- of-limit
threshold
0112 H
Out-of-limit
detection
type
0113 H
unsigned int
2 bytes
R/W
0 ... 1
0: over, 1: below
Alarm port
0114 H
unsigned int
2 bytes
R/W
0 ... 3
0: off
1: alarm output to relay
output 1
2: alarm output to relay
output 2
3: alarm output to output
ports 1 and 2
Alarm 2
0115 H ...
0119 H
10 bytes
R/W
See Alarm 1
Alarm 3
011A H ...
011E H
10 bytes
R/W
See Alarm 1
Alarm 4
011F H ...
0123 H
10 bytes
R/W
See Alarm 1
Alarm 5
0124 H ...
0128 H
10 bytes
R/W
See Alarm 1
Alarm 6
0129 H ...
012D H
10 bytes
R/W
See Alarm 1
Parameter Address
Data
Type
Length
R/W
Data
Range
Remark