Functions
3.12 Digital Input and Output Interface
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-
4
, Release Date
06.2018
21
3.12
Digital Input and Output Interface
Power Pulse Output
This meter provides two power pulse outputs: active and reactive, with internal opto-isolation, pulse output
width (80±20) ms, maximum allowable passing current 10 mA (DC) and operating voltage range 5 V to 80 V
(DC).
Figure 3-1
Circuit Diagram of Power Pulse Output Interface
Binary Input Interface
This product is provided with 4-digit binary inputs interface based on passive dry contact. Terminals are identi-
fied as DI1, DI2, DI3, DI4 and COM. COM is the common terminal.
Figure 3-2
Circuit Diagram of Binary Input Interface