Operation and Display
4.2 Cyclic Display
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-
4
, Release Date
06.2018
25
Code list of optional settings in area A:
Code list of optional settings in area B:
Data item
Data type (current value)
Data item
Data type (current
value)
Tran-
sient
Maximun
(previous 1
to 3 months)
Minimum
(previous 1
to 3 months)
Transient
2
nd
to 50
th
Phase voltage
0
1 (2 ... 4)
5 (6 ... 8)
Voltage unbalance rate
66
/
Line voltage
9
10 (11 ... 13) 14 (15 ... 17) Current unbalance rate
67
/
Current
18
19 (20 ... 22) 23 (24 ... 26) Voltage eligibility rate
68
/
Neutral current
27
28 (29 ... 31)
V
Voltage distortion rate
69
/
Active power
36
37 (38 ... 40) 41 (42 ... 44) Current distortion rate
70
/
Reactive power
45
46 (47 ... 49) 50 (51 ... 53) Fundamental voltage
71
72 ... 120
Apparent power
54
55 (56 ... 58) 59 (60 ... 62) Fundamental current
121
120 ... 170
Power factor
63
/
/
Second harmonic
voltage ratio
171
172 ... 219
Phase angle
64
/
/
Second harmonic
current ratio
220
221 ... 268
Data item
Data: 7 continuous codes express total, tariff 1 to tariff 6 in order; 4 continuous
codes express current month, previous 1 to 3 months in order.
Current
Previous
1 month
Previous 2
month
Previous 3
month
Phase A
Phase B
Phase C
Import active power
351 ... 357 358 ... 364 365 ... 371 372 ... 378 379 ... 382 383 ... 386 387 ... 390
Export active power
391 ... 397 398 ... 404 405 ... 411 412 ... 418 419 ... 422 423 ... 426 427 ... 430
Total active power
431 ... 437 438 ... 444 445 ... 451 452 ... 458 459 ... 462 463 ... 466 467 ... 470
Net active power
471 ... 477 478 ... 484 485 ... 491 492 ... 498 499 ... 502 503 ... 506 507 ... 510
Import reactive power 511 ... 517 518 ... 524 525 ... 531 532 ... 538 539 ... 542 543 ... 546 547 ... 550
Export reactive power 551 ... 557 558 ... 564 565 ... 571 572 ... 578 579 ... 582 583 ... 586 587 ... 590
Total reactive power
591 ... 597 598 ... 604 605 ... 611 612 ... 618 619 ... 622 623 ... 626 627 ... 630
Net reactive power
631 ... 637 638 ... 644 645 ... 651 652 ... 658 659 ... 662 663 ... 666 667 ... 670
Import active demand 671 ... 677 678 ... 684 685 ... 691 692 ... 698
Export active demand 699 ... 705 706 ... 712 713 ... 719 720 ... 726
Import reactive
demand
727 ... 733 734 ... 740 741 ... 747 748 ... 754
Export reactive
demand
755 ... 761 762 ... 768 769 ... 775 776 ... 782
Import apparent
demand
783 ... 789 790 ... 796 797 ... 803 804 ... 810
Export apparent
demand
811 ... 817 818 ... 824 825 ... 831 832 ... 838
Phase A forward
current demand
839 ... 845 846 ... 852 853 ... 859 860 ... 866
Phase B forward
current demand
867 ... 873 874 ... 880 881 ... 887 888 ... 894
Phase C forward
current demand
895 ... 901 902 ... 908 909 ... 915 916 ... 922
Frequency
923
Data
924