Figure 21.
Connection of Bus at Shipping Split
Electrical Connections
28
A:
Shipping split, as shipped. Insulation boots are factory
installed in correct location. Bus bars and hardware are
mounted on a temporary shipping bracket in the one of the
units to be connected. (Bus bars and hardware may be
packed separately in unusual situations).
B:
Shipping split assembly in progress. Insulation boots have
been removed, and bus bars have been installed. Connection
bolts have been correctly torqued. Unit is ready for reinstalla-
tion of insulation boots.
C:
Insulation boots have been reinstalled. Unit is ready for
reinstallation of main bus compartment barrier (designated R
in
Figure 25
).
D:
Taped bus joint configuration, used for joints where a boot
is not available. This illustrates a taped connection for multiple
cable terminals. After cables have been installed, the cable
terminations and the exposed bus must be insulated.
03367-89
03365-89
03364-89