Installation Instructions

Document No. 129-479

November 13, 2012

 

Series 2300 Room Units 
for TALON® Controllers

 

 

Item Number 129-479, Rev. HA 

 

Page 1 of 6 

Product Description 

These room units measure temperature in the 
occupied space in which they are installed. Models 
with display allow users to view the measured 
temperature value. A version with temperature 
setpoint adjustment is also offered. 

These devices are intended for use with appropriate 
signal input on a TALON Controller. The effective 
sensing and setpoint range is 55°F to 95°F (13°C to 
35°C). 

These room units can be mounted on electrical 
boxes, stud-type mounting brackets, or drywall. 
Obtain the necessary mounting hardware and follow 
the appropriate mounting procedures for the type of 
installation required. 

Product Numbers 

QAA2312.xWxN 

QAA2330.xWxx 

QAA23SS.xWxN 

QAA23SS.xWxx 

Accessories 

AQA2200-INTL Room Unit Back Plate (10-pack) 

AQA2200-2X4 Room Unit Back Plate (Single) 

NOTE: 

If installing the Back Plate, discard the 
metric screws provided with the Back Plate 
and utilize the Room Unit mounting screws. 

Caution Notations 

CAUTION 

Equipment damage or loss of 
data may occur if you do not 
follow a procedure as 
specified. 

Expected Installation Time 

20 minutes 

Required Tools 

 

Sizes 1 and 2 Phillips screwdrivers 

 

Small and medium flat-blade screwdrivers 

 

1/16-inch hex key 

 

Medium-duty electric drill 

 

3/16-inch (4.8 mm) drill bit 

 

One-inch (25 mm) hole saw 

 Small 

level 

 Tape 

measure 

 

Marker or pencil 

Prerequisites 

 

Review these instructions before beginning. 

 

Installed: appropriate field wiring within the 
maximum wiring run length for the individual 
equipment controller. The maximum 
recommended length is 100 feet (30 m). 

 

All wiring must comply with National Electric 
Code (NEC) and local regulations. 

  

 

Figure 1.  QAA23xx.EWTN, and QAA23xx.FWTN  

Room Units. 

Содержание Series 2300

Страница 1: ...QAA2330 xWxx QAA23SS xWxN QAA23SS xWxx Accessories AQA2200 INTL Room Unit Back Plate 10 pack AQA2200 2X4 Room Unit Back Plate Single NOTE If installing the Back Plate discard the metric screws provided with the Back Plate and utilize the Room Unit mounting screws Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Expected Installation...

Страница 2: ...o plastic wall anchors flush to below the wall surface for stable mounting of the device 3 Cut a 1 inch 25 mm center hole with a hole saw 4 Pull about three inches 75 mm of the cable through the hole in the base plate 5 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior t...

Страница 3: ... locator by removing the two screws and lightly rocking the locator to pull it free 2 Untie the twist tie and pull about three inches 75 mm of the room unit cable through the hole in the base plate 3 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior to mounting to the wa...

Страница 4: ...or Controller a 500 ohm resistor must be wired in series with the setpoint termination on the Predator Controller and the Override termination 8 on the Room Sensor See Figure 6 and Figure 7 for the complete wiring diagrams for the two different style controllers The installation is now complete 1 2 3 4 5 6 7 8 9 10 11 12 SEN0485R1 Figure 5 Typical Wiring Base All terminals may not be present Pin N...

Страница 5: ...0644R1 500 ohm Orange White Orange White Green White Blue Blue Green 5 SetPoint Bypass 6 Room Temp 2 LonNetwork 4 Common 3 Service Pin LCD Power 1 LonNetwork Color Pin Wire Twisted Pair Twisted Pair Twisted Pair P I 9 11 Figure 7 Pin No Function QAA2312 EWTN 2 Temperature 3 Temp_Common QAA2330 EWxC 2 Temperature 3 Temp_Common 7 LON1 8 LON2 QAA23SS EWxN 1 DC or ACH 2 DC or ACN GND 3 Temperature Out...

Страница 6: ...300 100 VA DC ACH DC ACN GND Signal Out Powered By Class 2 100VA Isolated AC L N E With Class 2 100 VA Output Isolated AC Supply See Controller Installation Instructions L N E Note See Caution NOTE Externally AC powered 2300 Room Units require controller common and all AC secondary neutral ACN to be earth grounded and may be used on the same controller with other room units powered by internal sen...

Отзывы: