Installation Instructions
Document No. 129-479
November 13, 2012
Series 2300 Room Units
for TALON® Controllers
Item Number 129-479, Rev. HA
Page 1 of 6
Product Description
These room units measure temperature in the
occupied space in which they are installed. Models
with display allow users to view the measured
temperature value. A version with temperature
setpoint adjustment is also offered.
These devices are intended for use with appropriate
signal input on a TALON Controller. The effective
sensing and setpoint range is 55°F to 95°F (13°C to
35°C).
These room units can be mounted on electrical
boxes, stud-type mounting brackets, or drywall.
Obtain the necessary mounting hardware and follow
the appropriate mounting procedures for the type of
installation required.
Product Numbers
QAA2312.xWxN
QAA2330.xWxx
QAA23SS.xWxN
QAA23SS.xWxx
Accessories
AQA2200-INTL Room Unit Back Plate (10-pack)
AQA2200-2X4 Room Unit Back Plate (Single)
NOTE:
If installing the Back Plate, discard the
metric screws provided with the Back Plate
and utilize the Room Unit mounting screws.
Caution Notations
CAUTION
Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.
Expected Installation Time
20 minutes
Required Tools
•
Sizes 1 and 2 Phillips screwdrivers
•
Small and medium flat-blade screwdrivers
•
1/16-inch hex key
•
Medium-duty electric drill
•
3/16-inch (4.8 mm) drill bit
•
One-inch (25 mm) hole saw
•
Small
level
•
Tape
measure
•
Marker or pencil
Prerequisites
•
Review these instructions before beginning.
•
Installed: appropriate field wiring within the
maximum wiring run length for the individual
equipment controller. The maximum
recommended length is 100 feet (30 m).
•
All wiring must comply with National Electric
Code (NEC) and local regulations.
Figure 1. QAA23xx.EWTN, and QAA23xx.FWTN
Room Units.