Connection
5.4 Wiring test
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
77
Circuit diagram of three-phase device 80 A (outputs depend on device type)
*
The fuse in the voltage measuring input is only used for cable protection.
Tightening torque
Cable cross-section
(mm
2
)
L1 / L2 / L3 / N / 80 A
1.8 … 2.2
(15.9 ... 19.5)
2.5 … 25
Tariff input
0.44 … 0.53
(3.9 ... 4.7)
0.2 … 2.5
RS 485 / M-Bus / S0
0.14 … 0.16
(1.2 ... 1.4)
0.2 … 2.5
Parameterization
Parameterization of the devices is described in chapter Parameterization (Page 33).
5.4
Wiring test
If the wiring is incorrect and the device detects an energy flow in the wrong direction, the
message
Err 3
appears on the display.
This error is either caused by incorrect wiring of the current inputs (terminals L
↑ and
L
↓) or
by incorrect voltage wiring (terminals N - L
↑).
Energy is not counted under these conditions.
Содержание Sentron 7KT PAC 1600
Страница 1: ......
Страница 2: ......
Страница 8: ......
Страница 12: ...Introduction 1 5 Qualified personnel 7KT16 energy meter 10 Equipment Manual 09 2020 2514284147 04 ...
Страница 16: ......
Страница 70: ...Description 3 6 Supporting software 7KT16 energy meter 68 Equipment Manual 09 2020 2514284147 04 ...
Страница 80: ...Connection 5 4 Wiring test 7KT16 energy meter 78 Equipment Manual 09 2020 2514284147 04 ...
Страница 98: ......
Страница 106: ...Technical data 8 2 Labels on the enclosure 7KT16 energy meter 104 Equipment Manual 09 2020 2514284147 04 ...
Страница 108: ...Dimensional drawings 9 2 Three phase device 7KT16 energy meter 106 Equipment Manual 09 2020 2514284147 04 ...
Страница 113: ......
Страница 114: ......