Accessories
3.5 External accessories
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
124
Manual, 10/2018, L1V30499596002-01
Locking mechanism to prevent movement of the withdrawable CB
With the locking device for padlocking on the guide frame, the circuit breaker is secured
against racking in the guide frame. The positions CONNECT, TEST and DISCONNECT can
be locked.
Locking is performed on the guide frame with up to three padlocks (diameter 8 mm / 0.32").
The circuit breaker can then no longer be racked in or out.
The padlocks are not included in the scope of delivery of the locking device and must be
provided by the customer.
Additional locking device that permits only locking in breaker position DISCONNECT with the
cylinder lock or padlock
When you use cylinder locks, locking can be limited to locking in the DISCONNECT position
by the additional accessory "Locking mechanism to prevent movement of the withdrawable
CB in the disconnected position". Locking in the CONNECT and TEST positions is then no
longer possible. Locking itself is performed with the two devices stated above