Modbus RTU Interface Module for SED2
Technical Instructions
Document Number 155-767
February 25, 2009
Siemens Industry, Inc.
Page 5
Hardware Setup
Continued
Default Configuration
Table 4. Configuration Options.
Parameter
Options
Default
Protocol
Interface Module ASCII
Interface Module RTU
Interface Module
RTU
Interface
Module ID
1… 254
2
Baud Rate
1200 bps
4800 bps
9600 bps
9600 bps
19200 bps
38400 bps
57600 bps
115200 bps
9600 bps
Data Bits
7
8
8
Parity
None
Even
Odd
Even
Stop Bits
1
2
1
Changing the
Configuration
The configuration stored in the Interface Module may be changed from the default
configuration by entering CONFIGURATION Mode.
1. Attach a configuration cable between the LOCAL port and a serial port on a
computer.
2. Start a terminal program, such as HyperTerminal, on the computer, and connect
using the following setting:
•
Baud = 9600 bps
•
Data bits = 8
•
Parity = None
•
Stop bits = 1
•
Flow control = None
3. With the Programming Switch set to RUN, apply power to the Interface Module,
and press the
ENTER
key within five seconds of startup. See Figure 9.