![Siemens SED2-MODBUS2 Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/siemens/sed2-modbus2/sed2-modbus2_technical-instructions_377362012.webp)
Technical Instructions
Modbus RTU Interface Module for SED2
Document Number 155-767
February 25, 2009
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners.
© 2009 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
+ 1 847-215-1000
Your feedback is important to us. If you have comments
about this document, please send them to
Printed in the USA
Page 12
Interface Module Registers, Continued
Table 8. Interface Module Registers.
Register
Number
Description
Units
Scaling
Factor
On Text
Off Text
SED2
Reference
Or Range
40033
OUTPUT VOLTS
V
1
0 – 65535
r0025
40034
FWD REV
––
1
FWD
REV
ZSW:14
40035
STOP RUN
––
1
STOP
RUN
ZSW:2
40036
AT MAX FREQ
––
1
MAX
NO
ZSW:10
40037
CONTROL MODE
––
1
SERIAL
LOCAL
ZSW:9
40038
ENABLED
––
1
ON
OFF
ZSW:0
40039
READU TO RUN
––
1
READY
OFF
ZSW:1
40040
ANALOG IN 1
PCT
10
-300.0 – 300.0
r0754/0
40041
ANALOG IN 2
PCT
10
-300.0 – 300.0
r0754/1
40042
ANALOG OUT 1
PCT
10
-100.0 – 100.0
r0774/0
40043
ANALOG OUT 2
PCT
10
-100.0 – 100.0
r0774/1
40044
FREQ ACTUAL
PCT
10
00.0 – 100.0
HIW
40045
PID SETP OUT
PCT
10
-100.0 – 100.0
r2250
40046
PID OUTPUT
PCT
10
-100.0 – 100.0
r2294
40047
PI FEEDBACK
PCT
10
-100.0 – 100.0
r2266
40048
DIGITAL IN 1
––
1
ON
OFF
r0722:0
40049
DIGITAL IN 2
––
1
ON
OFF
r0722:1
40050
DIGITAL IN 3
––
1
ON
OFF
r0722:2
40051
DIGITAL IN 4
––
1
ON
OFF
r0722:3
40052
DIGITAL IN 5
––
1
ON
OFF
r0722:4
40053
DIGITAL IN 6
––
1
ON
OFF
r0722:5
40054
FAULT
––
1
FAULT
OK
ZSW:3
40055
LAST FAULT
––
1
0 – 65535
r0947
40056
1ST FAULT
––
1
0 – 65535
r0947
40057
2ND FAULT
––
1
0 – 65535
r0947
40058
3RD FAULT
––
1
0 – 65535
r0947
40059
WARNING
––
1
WARN
OK
ZSW:7
40060
LAST WARNING
––
1
0 – 65535
r2110
40061
INVERTER VER
––
100
0.00 – 655.35
r0018
40062
DRIVE MODEL
––
1
0 – 655.35
r0200
40063
FREQ ACTUAL
––
1
0 – 4000h (4000H = 100%)
HIW