Siemens SED2-MODBUS2 Скачать руководство пользователя страница 11

Modbus RTU Interface Module for SED2 

Technical Instructions 

 

Document Number 155-767 

 

February 25, 2009 

Page 11 

Siemens Industry, Inc. 

Interface Module Registers, Continued 

Table 7.  Interface Module Registers.  

Register 

Number 

Description 

Units 

Scaling Factor 

On Text 

Off Text 

SED2 

Reference  

Or Range 

40001 

WDOG TIME 

MS 

0 – 65535 

–– 

40002 

WDOG ACTION 

–– 

STOP DRIVE 

NO ACTION 

–– 

40003 

FREQ REF 

PCT 

100 

0.00 – 4000h (4000h = 100%) 

HSW 

40004 

RUN ENABLE 

–– 

ENABLE 

OFF 

STW:3 

40005 

CMD FWD REV 

–– 

REV 

FWD 

STW:11 

40006 

CMD START 

–– 

START 

OFF 

STW:0 

40007 

FAULT ACK 

–– 

ACK 

NO ACK 

STW:7 

40008 

PID SETP REF 

PCT 

10 

-200.0 – 200.0 

P2240 

40009 

ENABLE PID 

–– 

ENABLE 

DISABLE 

P2200 

40010 

CURRENT LMT 

PCT 

10 

10.0 – 400.0 

P0640 

40011 

ACCEL TIME 

SEC 

100 

0.00 – 650.00 

P1120 

40012 

DECEL TIME 

SEC 

100 

0.00 – 650.00 

P1121 

40013 

HAND AUTO 

–– 

HAND 

AUTO 

P0718 

40014 

DIGITAL OUT 1 

–– 

ON 

OFF 

P0731 

40015 

DIGITAL OUT 2 

–– 

ON 

OFF 

P0732 

40016 

FREQ MAX 

HZ 

100 

1.00 – 650.00 

P2000 

40017 

PID UP LMT 

PCT 

10 

-200.00 – 200.00 

P2291 

40018 

PID LO LMT 

PCT 

10 

-200.00 – 200.00 

P2292 

40019 

P GAIN 

–– 

1000 

0.000 – 65.000 

P2280 

40020 

I GAIN 

SEC 

0 – 60 

P2285 

40021 

D GAIN 

–– 

0 – 60 

P2274 

40022 

FEEDBK GAIN 

PCT 

100 

0.00 – 500.00 

P2269 

40023 

LOW PASS 

–– 

100 

0.00 – 60.00 

P2265 

40024 

FREQ OUTPUT 

HZ 

10 

-650.0 – 650.0 

r0024 

40025 

SPEED 

RPM 

-16250 – 16250 

r0022 

40026 

CURRENT 

10 

0 – 1638.3 

r0027 

40027 

TORQUE 

NM 

10 

-3250.0 – 3250.0 

r0031 

40028 

ACTUAL PWR 

KW 

100 

0 – 655.35 

r0032 

40029 

TOTAL KWH 

KWH 

0 – 65535 

r0039 

40030 

DC BUS VOLTS 

0 – 65535 

r0026 

40031 

REFERENCE 

Hz 

10 

-650.0 – 650.0 

r0020 

40032 

RATED PWR 

KW 

100 

0 – 655.35 

r0206 

 

Содержание SED2-MODBUS2

Страница 1: ...roGate II Interface module Local cable for USS communication with SED2 Network cable for ModBus communication with Building Automation controller Installation documentation Required Tools Personal computer for configuring device prior to operation Configuration Kit SED2 MODBUS2_KIT containing External Power Supply for the MicroGate II 9 pin female to 9 pin female Serial Null Modem Cable Installati...

Страница 2: ...serial port from the SED2 See Figure 2 WARNING Do not connect the external 9 Vdc power supply and pin 9 of the LOCAL cable at the same time Programming Switch The Programming PRG Switch on the Interface Module should always be in the RUN position up for normal operations and configuration The PRG position is used strictly for loading firmware at the factory The Interface Module comes with two seri...

Страница 3: ...nection type may vary among different installations the cable ends are stripped wires to provide maximum flexibility Figure 4 RS485 Network Cable Figure 5 Four Wire Local Port Cable A four wire cable Figure 5 connects the LOCAL port on the Interface Module to an SED2 The cable ends in stripped wires to facilitate a connection to the SED2 drive terminals shown below CAUTION SED2 drive power should ...

Страница 4: ... power Off No power applied to the device Run Mode Flashing Green 250 ms On 250 ms Off Interface Module is operating normally in RUN Mode Configuration Mode Flashing Green 1 5 sec on 1 5 sec Off Interface Module is in CONFIGURATION Mode Fatal Error Flashing Yellow 250 ms On 250 ms Off Interface Module has experienced a fatal error and has halted communication NOTE If the Interface Module has been ...

Страница 5: ...9600 bps Data Bits 7 8 8 Parity None Even Odd Even Stop Bits 1 2 1 Changing the Configuration The configuration stored in the Interface Module may be changed from the default configuration by entering CONFIGURATION Mode 1 Attach a configuration cable between the LOCAL port and a serial port on a computer 2 Start a terminal program such as HyperTerminal on the computer and connect using the followi...

Страница 6: ...rface Module is in CONFIGURATION Mode it will send its current configuration to the terminal program Figure 9 MicroGate II Configuration Display Table 5 Keyboard Navigation Use the UP and DOWN arrows on the computer keyboard to navigate to the field you want to change Change values with the LEFT and RIGHT arrows Save Configuration Navigate to here and press ENTER to save changes ...

Страница 7: ... Table 3 Table 6 SED2 Parameter Settings to Communicate with the MicroGate II SED2 Parameter Function Setting Value P0003 User Access Level 3 Expert Level P0700 0 Command Source 5 if Starting Stopping VFD from Modbus otherwise DO NOT change P1000 0 Frequency Setpoint Source 5 if Setting the Frequency from Modbus otherwise DO NOT change P2009 0 USS Normalization 0 Disabled P2010 0 USS Baud Rate 7 1...

Страница 8: ...N 40002 to 1 so that the SED2 stops on loss of communications with the Modbus master To deactivate the Interface Module Host Watchdog Function set WDOG ACTION to 0 SED2 Parameter 2014 USS Telegram Off Time controls a Watchdog timer function for the USS port Once the Interface Module establishes communications with the SED2 if the Interface Module stops communicating with the SED2 the SED2 automati...

Страница 9: ...ommunications by issuing a start command from the source and checking the feedback on the Modbus master device to ensure that it reads proper values in the appropriate Registers Modbus Interface Module with Network as Command Source 1 To verify that the Interface Module and SED2 are set up correctly set P0700 0 and P1000 0 to a value of 5 so that the SED2 can be controlled from the Interface Modul...

Страница 10: ...om the SED2 Both Registers are scaled so that a value of 4000th represents 100 of the actual frequency FREQ SCALED 40044 contains a scaled version of the HIW data so that a value of 2000 in the register represents the value 4000h in the USS protocol response and 100 of the maximum frequency STW and HSW refer to the 1st and 2nd control words respectively of PZD data included in every poll sent from...

Страница 11: ...CT 10 10 0 400 0 P0640 40011 ACCEL TIME SEC 100 0 00 650 00 P1120 40012 DECEL TIME SEC 100 0 00 650 00 P1121 40013 HAND AUTO 1 HAND AUTO P0718 40014 DIGITAL OUT 1 1 ON OFF P0731 40015 DIGITAL OUT 2 1 ON OFF P0732 40016 FREQ MAX HZ 100 1 00 650 00 P2000 40017 PID UP LMT PCT 10 200 00 200 00 P2291 40018 PID LO LMT PCT 10 200 00 200 00 P2292 40019 P GAIN 1000 0 000 65 000 P2280 40020 I GAIN SEC 1 0 6...

Страница 12: ...D REV 1 FWD REV ZSW 14 40035 STOP RUN 1 STOP RUN ZSW 2 40036 AT MAX FREQ 1 MAX NO ZSW 10 40037 CONTROL MODE 1 SERIAL LOCAL ZSW 9 40038 ENABLED 1 ON OFF ZSW 0 40039 READU TO RUN 1 READY OFF ZSW 1 40040 ANALOG IN 1 PCT 10 300 0 300 0 r0754 0 40041 ANALOG IN 2 PCT 10 300 0 300 0 r0754 1 40042 ANALOG OUT 1 PCT 10 100 0 100 0 r0774 0 40043 ANALOG OUT 2 PCT 10 100 0 100 0 r0774 1 40044 FREQ ACTUAL PCT 1...

Отзывы: