background image

The SBGA-34 can generate steady, temporal-3 or temporal-4 tone when powered from 24VDC UL listed
aux power source or can be configured to follow the NAC tone pattern that is dependent of the panel
being used. Refer to the Tone Selection section to configure the units for stand-alone operation.

APPLICATION NOTE

The SBGA-34 is a UL268 and UL464 listed smoke detector supplementary devices which combines
detector base and audible device functions. When used in conjunction with the listed compatible Siemens
equipment, the SBGA-34 may be used in lieu of single/multiple station smoke alarms to achieve
enhanced, system level functionality.

When used to follow the NAC tone pattern, the SBGA-34 must be set to steady tone and the panel it is
connected to must be configured accordingly for the desired application. This allows the SBGA-34 to
transition from one tone to another (example from temporal 4 to temporal 3) if the proper criteria is met
and allows it to be synchronized with the NAC zone that it is connected.

Typical applications are sleeping rooms in hotels, guest suites, dormitories, day-care, residential boards
and care facilities as designated in NFPA 72.

CONSTRAINTS

1.

SBGA-34 supervisory current is drawn from the detector loop in which their associated

detector is connected. This must be included in the determining the battery size of the panel.

2.

SBGA-34 alarm current is drawn both from external power supply source and the detector

loop in which their associated detector is connected. Care must be taken to verify that this is

properly entered during its battery calculation requirements.

3.

SBGA-34 audible section can be energized by an auxiliary power supply such as PS-35 with

AU-30U (System 3 power supply), PAD-3 / PAD 4 (Auxiliary Power Supply / NAC Extender) or

through the NAC circuit. The SBGA-34 can also be powered by a UL listed 24VDC Auxiliary

power supply/ Notification Appliance Circuit listed for fire protection signaling use.

4.

The maximum number of SBGA-34 is related to the maximum current rating and power line

resistance of the auxiliary power supplies applied on the SBGA-34. Refer to the related

installation instructions of the auxiliary power supply. It is also related to the maximum current

rating of the loop. Refer to the installation instructions mentioned in the fifth constraint.

5.

The maximum loop line resistance cannot exceed the maximum line resistance of the loop

driver the SBGA-34 is connected to specified in their respective installation instructions. For

Electrical Ratings

Voltage Rating

17 – 31VDC

Special Applications

Current

Supervisory:
Loop: 0.6mA
External Power Supply:
0mA

Alarm:
Loop: 2.8mA
External Power Supply:
56mA

Audibility Measurements at 10 ft.

UL464

79dBA

UL268

85dBA

ULCS525

85dBA

Содержание SBGA-34

Страница 1: ...35 AE 30U 24 VDC BATTERY PS 35 POWER INPUT 120 VAC 50 60 Hz CONNECTED TO GROUND REFERENCE OF THE PANELS IT S CONNECTED TO REFER TO TABLE X FOR GROUND CONNECTION LINE 2 LINE 1 LINE 1 LINE 2 LINE 2 LINE 1 FOR CONNECTION TO SLC LOOP FROM DLC LOOP OF SYSTEM OR FS DLC LOOP OF FS 250 SYSTEM FIREFINDER XLS TO NEXT SBGA 34 DB3S DB X3RS OR DB 11 4 4 4 4 8 8 12 PIN PLUG 5 5 5 5 9 6 6 6 6 10 3 3 3 3 7 7 2 2 ...

Страница 2: ...E 3 NOTE 3 Figure 2 Installation Wiring Diagram for SBGA 34 Audible Powered by ZIC 4A FireFinder XLS System 1 Polarity shown in active state at terminals 1 and 2 of SBGA 34 and 1 4 of ZIC 8B Proper polarity must be maintained or audible base will not operate properly Each audible base must be tested to verify operation 2 Tone selection refer to page 7 for more information 3 SBGA 34 terminals 5 8 a...

Страница 3: ...4 5 6 1b 1a 8 8 7 7 6 6 5 5 1 1 2 2 3 3 4 4 TO NEXT ADDRESSABLE DEVICE LINE 1 LINE 2 LINE 1 LINE 2 24K 1 2W 5 FROM FS DLC OR FDLC LOOP OF FS 250 OR FS 250C SYSTEM NOTE 2 NOTE 2 NOTE 3 NOTE 3 TB12 TB13 4 3 4 3 2 1 2 1 TB8 TB7 NO NC C NC NO C Figure 4 Installation Wiring Diagram for SBGA 34 Audible Powered by NAC Circuits FS 250 FS 250C Systems and MPC6000 MPC7000 SBGA 34 SBGA 34 5 6 1b 1a 8 8 7 7 6...

Страница 4: ... for SBGA 34 Audible connected to FC901 Panel 1 Polarity shown in active state at terminals 1 and 2 of SBGA 34 and 1 1 2 and 2 of FC2025 2050 FC922 924 NAC circuits Proper polarity must be maintained or audible base will not operate properly Each audible base must be tested to verify operation 2 Tone selection refer to page 7 for more information 3 SBGA 34 terminals 5 8 are polarity insensitive Li...

Страница 5: ...ctor is connected This must be included in the determining the battery size of the panel 2 SBGA 34 alarm current is drawn both from external power supply source and the detector loop in which their associated detector is connected Care must be taken to verify that this is properly entered during its battery calculation requirements 3 SBGA 34 audible section can be energized by an auxiliary power s...

Страница 6: ...minimum of 14 AWG must be used 9 Even though no specific spacing is allocated to the detectors used with this base refer to NFPA Standard 72 National Fire Alarm Code and the installation instructions of the detector being used see Table 1 For additional information on the used in an individual system refer to the installation instructions for that particular module or contact your authorized Sieme...

Страница 7: ...NEXT SBGA 34 DB 11 DB 3S or DB X3RS POWER SUPPLY POLARITY SHOWN IN ACTIVE STATE _ SBGA 34 4 3 2 1 JUMPER FOR TONE SELECTION LINE 1 LINE 2 LINE 1 LINE 2 FROM P2 LOOP NOTE Use both Terminals or leads for connection break wire run to provide electrical supervision Figure 8 SBGA 34 Audible Base Terminal Blocks TONE SELECTION With audible base Model SBGA 34 the user can choose either temporal tone Temp...

Страница 8: ...udible Base Model SBGA 34 attaches only to a 4 inch square electrical box with extension Mounting the Base 1 Route all wires out from the outlet box 2 Make connections directly to the audible base terminals located on the back of the base Refer to the related Installation Wiring Diagram 3 After all bases are installed check loop continuity For SBGA 34 Detector loop continuity check refer to the DP...

Отзывы: