the DLC module (XLS panel), refer to the DLC installation instructions, P/N 315-033090. For

the FCI2016-U1/FCI2017-U1 module (250pt/500pt Desigo/Cerberus panel), refer to the FS20

Installation Instructions, P/N A6V10315038. For the FC901MB-U1 (50pt Desigo/Cerberus

panel), refer to the FC360 Installation Instructions, P/N A6V10336754.

6.

T-tapping of the notification appliance circuit is not allowed.

7.

When SBGA-34 Is powered from external power supply source, care must be taken to insure

that proper ground fault detection is not compromised In typical application where the

external power source do not have the capability for ground fault detection, its ground

potential must be connected to the ground potential of the FACP to allow for ground fault

supervision.

8.

A minimum of 14 AWG must be used.

9.

Even though no specific spacing is allocated to the detectors used with this base, refer to
NFPA Standard 72 National Fire Alarm Code and the installation instructions of the detector
being used (see Table 1).

For additional information on the used in an individual system, refer to the installation instructions for that
particular module or contact your authorized Siemens Industry, Inc. representative.

DETECTOR PLACEMENT

The model SBGA-34 is compatible to the detectors listed in Table 1:

TABLE 1

COMPATIBLE DETECTORS

Detector

Inst. Instr. P/N

HFP-11/HFPT-11

315-033290

HFPO-11

315-034800

SFP-11/SFPT-11*

315-033290C

SFPO-11*

315-033290C

8710, 8712, 8713

315-033290FA

FDO421

A6V10323926

FDOT421

A6V10323934

FDT421

A6V10323930

OP921

A6V10323928

OH921

A6V10323936

HI921

A6V10323932

FDOOT441

A6V10324655

FDOOTC441

A6V10324657

OOHC941

A6V10324661

OOH941

A6V10324659

*SFP-11, SFPT-11 and SFPO-11
detectors are approved for use in
Canada only.

Содержание SBGA-34

Страница 1: ...35 AE 30U 24 VDC BATTERY PS 35 POWER INPUT 120 VAC 50 60 Hz CONNECTED TO GROUND REFERENCE OF THE PANELS IT S CONNECTED TO REFER TO TABLE X FOR GROUND CONNECTION LINE 2 LINE 1 LINE 1 LINE 2 LINE 2 LINE 1 FOR CONNECTION TO SLC LOOP FROM DLC LOOP OF SYSTEM OR FS DLC LOOP OF FS 250 SYSTEM FIREFINDER XLS TO NEXT SBGA 34 DB3S DB X3RS OR DB 11 4 4 4 4 8 8 12 PIN PLUG 5 5 5 5 9 6 6 6 6 10 3 3 3 3 7 7 2 2 ...

Страница 2: ...E 3 NOTE 3 Figure 2 Installation Wiring Diagram for SBGA 34 Audible Powered by ZIC 4A FireFinder XLS System 1 Polarity shown in active state at terminals 1 and 2 of SBGA 34 and 1 4 of ZIC 8B Proper polarity must be maintained or audible base will not operate properly Each audible base must be tested to verify operation 2 Tone selection refer to page 7 for more information 3 SBGA 34 terminals 5 8 a...

Страница 3: ...4 5 6 1b 1a 8 8 7 7 6 6 5 5 1 1 2 2 3 3 4 4 TO NEXT ADDRESSABLE DEVICE LINE 1 LINE 2 LINE 1 LINE 2 24K 1 2W 5 FROM FS DLC OR FDLC LOOP OF FS 250 OR FS 250C SYSTEM NOTE 2 NOTE 2 NOTE 3 NOTE 3 TB12 TB13 4 3 4 3 2 1 2 1 TB8 TB7 NO NC C NC NO C Figure 4 Installation Wiring Diagram for SBGA 34 Audible Powered by NAC Circuits FS 250 FS 250C Systems and MPC6000 MPC7000 SBGA 34 SBGA 34 5 6 1b 1a 8 8 7 7 6...

Страница 4: ... for SBGA 34 Audible connected to FC901 Panel 1 Polarity shown in active state at terminals 1 and 2 of SBGA 34 and 1 1 2 and 2 of FC2025 2050 FC922 924 NAC circuits Proper polarity must be maintained or audible base will not operate properly Each audible base must be tested to verify operation 2 Tone selection refer to page 7 for more information 3 SBGA 34 terminals 5 8 are polarity insensitive Li...

Страница 5: ...ctor is connected This must be included in the determining the battery size of the panel 2 SBGA 34 alarm current is drawn both from external power supply source and the detector loop in which their associated detector is connected Care must be taken to verify that this is properly entered during its battery calculation requirements 3 SBGA 34 audible section can be energized by an auxiliary power s...

Страница 6: ...minimum of 14 AWG must be used 9 Even though no specific spacing is allocated to the detectors used with this base refer to NFPA Standard 72 National Fire Alarm Code and the installation instructions of the detector being used see Table 1 For additional information on the used in an individual system refer to the installation instructions for that particular module or contact your authorized Sieme...

Страница 7: ...NEXT SBGA 34 DB 11 DB 3S or DB X3RS POWER SUPPLY POLARITY SHOWN IN ACTIVE STATE _ SBGA 34 4 3 2 1 JUMPER FOR TONE SELECTION LINE 1 LINE 2 LINE 1 LINE 2 FROM P2 LOOP NOTE Use both Terminals or leads for connection break wire run to provide electrical supervision Figure 8 SBGA 34 Audible Base Terminal Blocks TONE SELECTION With audible base Model SBGA 34 the user can choose either temporal tone Temp...

Страница 8: ...udible Base Model SBGA 34 attaches only to a 4 inch square electrical box with extension Mounting the Base 1 Route all wires out from the outlet box 2 Make connections directly to the audible base terminals located on the back of the base Refer to the related Installation Wiring Diagram 3 After all bases are installed check loop continuity For SBGA 34 Detector loop continuity check refer to the DP...

Отзывы: