the DLC module (XLS panel), refer to the DLC installation instructions, P/N 315-033090. For
the FCI2016-U1/FCI2017-U1 module (250pt/500pt Desigo/Cerberus panel), refer to the FS20
Installation Instructions, P/N A6V10315038. For the FC901MB-U1 (50pt Desigo/Cerberus
panel), refer to the FC360 Installation Instructions, P/N A6V10336754.
6.
T-tapping of the notification appliance circuit is not allowed.
7.
When SBGA-34 Is powered from external power supply source, care must be taken to insure
that proper ground fault detection is not compromised In typical application where the
external power source do not have the capability for ground fault detection, its ground
potential must be connected to the ground potential of the FACP to allow for ground fault
supervision.
8.
A minimum of 14 AWG must be used.
9.
Even though no specific spacing is allocated to the detectors used with this base, refer to
NFPA Standard 72 National Fire Alarm Code and the installation instructions of the detector
being used (see Table 1).
For additional information on the used in an individual system, refer to the installation instructions for that
particular module or contact your authorized Siemens Industry, Inc. representative.
DETECTOR PLACEMENT
The model SBGA-34 is compatible to the detectors listed in Table 1:
TABLE 1
COMPATIBLE DETECTORS
Detector
Inst. Instr. P/N
HFP-11/HFPT-11
315-033290
HFPO-11
315-034800
SFP-11/SFPT-11*
315-033290C
SFPO-11*
315-033290C
8710, 8712, 8713
315-033290FA
FDO421
A6V10323926
FDOT421
A6V10323934
FDT421
A6V10323930
OP921
A6V10323928
OH921
A6V10323936
HI921
A6V10323932
FDOOT441
A6V10324655
FDOOTC441
A6V10324657
OOHC941
A6V10324661
OOH941
A6V10324659
*SFP-11, SFPT-11 and SFPO-11
detectors are approved for use in
Canada only.