Technical Instructions 

RWD62U Universal Controller 

Document Number 155-737 
January 14, 2005 

 

Software Tool 

An optional, user-friendly, Windows® 95 (or later) based software tool for controller 
application selection and parameter adjustment is available. It provides you with a 
printout of the controller settings. This tool allows controller programming prior to 
installation. 

Functions 

Controller Type 

The RWD62U is a stand-alone universal controller, which performs both primary and 
auxiliary control functions. The respective mode is defined by entering the 
corresponding configuration and setting parameters via the push buttons on the 
controller or the software tool. 

Main Functions 

The RWD62U controller can be programmed as follows: 

• 

One sequence: 

Y1 or Y2 

Reverse or direct acting 

• 

Two sequences: 

Y1 and Y2 

Reverse and direct acting or 

   

Y1 and Y2 

Reverse and reverse acting or 

   

Y1 and Y2 

Direct and direct acting 

NOTE: 

Direct Acting – As air temperature increases, the control output increases. 

Reverse Acting – As air temperature increases, the control output 
decreases. 

 

TH0599R3

= TEMPERATURE SENSOR

= AIR DAMPER ACTUATOR

= HEATING COIL

= COOLING COIL

= HEATING OR COOLING COIL (TWO-PIPE)

= FAN OR PUMP

= TIME CLOCK

= REMOTE SET POINT UNIT

= OUTSIDE AIR SENSOR

+

+

-

-

 

Figure 1.  Frequently Used Symbols in Application Drawings. 

 

TH0786R1

Y1

O

u

tput

V

o

lt

age

Setpoint

Setpoint

Temp.

 

Figure 2.  One Sequence Heat, Direct 

Acting or Reverse Acting 

(Application 10 to 19). 

Y1

O

u

tput

V

o

lt

age

Temp.

Y2

Setpoint

TH0787R1

Figure 3.  Two Sequence Heat, Two Direct 
Acting or Two Reverse Acting Sequences

(Application 20 to 29

). 

 

Y1

Setpoint

Temp

Y2

O

u

tput

V

o

lt

age

TH0788R1

Setpoint

 

Figure 4.  One Direct Acting Heat and One 

Direct Acting Cool or One Reverse Acting 

Heat and One Direct Acting Cool 

Sequence

 

(Application 30 to 39).

 

TH0789R1

Y1

Temp.

O

u

tput

V

o

lt

age

Setpoint

Setpoint

 

Figure 5.  One Direct Acting Cool or One 

Reverse Acting Cool Sequence 

(Application 40 to 49). 

Page 4 

 

Siemens Building Technologies, Inc. 

Содержание RWD62U

Страница 1: ... and Siemens Building Technologies program software NOTE For complete supporting technical documentation including training presentations see www us sbt siemens com hvp components Features Stand alone electronic temperature controller with P or P I response 24 Vac operating voltage Control application selectable via Application Number Active input scale can be selectable Limit and direction of the...

Страница 2: ... 1 Weight RWD62U Controller 10 4 oz 295 grams With packaging 12 24 oz 347 grams Analog Inputs X1 X2 Siemens Ni 1000 ohm 32 F 0 C Controller measuring range 58 F to 302 F 50 C to 150 C Maximum cable length for 14 AWG Maximum 984 ft 300 m Pt 1000 ohm at 32 F 0 C Controller measuring range 4 F to 356 F 20 C to 180 C Maximum cable length for 14 AWG Maximum 984 ft 300 m Analog voltages For measured var...

Страница 3: ...B Series 310 lb in Non Spring Return Actuators GBB Series 177 lb in Non Spring Return Actuators 155 176P25 155 177P25 GEB Series 132 in lb Non Spring Return Actuators 155 318P25 GCA Series 142 in lb Spring Return Actuators 155 173P25 155 174P25 155 175P25 GMA Series 62 in lb Spring Return Actuators 155 315P25 SKD Valve Actuator with proportional input 155 180P25 SKB SKC Valve Actuator with proport...

Страница 4: ... or Y1 and Y2 Direct and direct acting NOTE Direct Acting As air temperature increases the control output increases Reverse Acting As air temperature increases the control output decreases TH0599R3 TEMPERATURE SENSOR AIR DAMPER ACTUATOR HEATING COIL COOLING COIL HEATING OR COOLING COIL TWO PIPE FAN OR PUMP TIME CLOCK REMOTE SET POINT UNIT OUTSIDE AIR SENSOR Figure 1 Frequently Used Symbols in Appl...

Страница 5: ...D1 input Analog Outputs Each output Y1 Y2 can be configured for either reverse or direct acting The modulating voltage output Y controls the devices requiring a 0 to 10 Vdc signal Example X1 Y2 Y1 Temp Y TH0791R1 Figure 7 Constant Volume with Temperature Control Direct Acting Reverse Acting X1 Room temperature Y1 Heating direct action Y2 Cooling reverse action X1 Y2 Y1 Temp Y TH0811R1 Figure 8 Con...

Страница 6: ...corresponding adjustable range from 100 to 8000 units Cascade Control TH0794R1 X1 Y2 Y1 Temp Y X2 Figure 11 X2 Supply Air Temperature Sensor You can select the P I P I room supply air temperature cascade control In this case the virtual P I room temperature controller determines the setpoint within the limiter setpoints for the P I supply air temperature controller Maximum Priority NOTE You cannot...

Страница 7: ... contact between terminals D1 and M can be used to implement setpoint changeover for day night operation When the contact is open the setpoints for day operation are selected When the contact is closed the setpoints for night operation are selected During the night mode the following auxiliary functions are disabled remote setpoint absolute relative limiter setpoint compensation and maximum priori...

Страница 8: ...62U Universal Controller LCD The LCD shows the following information for normal operation Current operating values maximum four digits Current setpoints day night Application number Control sequencing diagram Auxiliary input value Selected auxiliary function Operating Buttons The controller has three operating buttons for the following functions The SELECT button is used to enter or save the value...

Страница 9: ...ansformers with double insulation they must be designed for 100 duty When using several transformers in one system the connection terminals G0 ground must be galvanically connected Supplying voltages above 24 Vac to low voltage connections may damage or destroy the controller or any other connected devices Connections to voltages exceeding 24 Vac endanger personal safety The ARG62 21 Protective Ho...

Страница 10: ...gram TH0801R1 Y1 G Y1 S1 D1 GO Y B M B M X1 X2 M M Y2 Y2 GO G Y X2 X1 M M M GO G 24 V SN 24 V SP N1 TOOL PC G G N1 RWD62U controller PC Personal computer S1 Time clock or switch SN System neutral SP System potential X1 Main input Termination G appears when X1 is an active sensor X2 Auxiliary input or remote setpoint Termination G appears when X2 is an active sensor Y1 Y2 Valve actuator 1 and 2 Dam...

Страница 11: ...tive owners 2005 Siemens Building Technologies Inc Siemens Building Technologies Inc 1000 Deerfield Parkway Your feedback is important to us If you have comments about this document please send Dimensions In Inches Millimeters TH0802R1 5 12 130 3 50 89 4 37 111 2 22 56 5 1 89 47 9 1 22 31 0 16 4 0 16 4 4 17 106 1 80 45 7 Figure 20 RWD62U Controller Dimensions TH0745R1 5 91 150 7 87 200 2 41 61 2 F...

Отзывы: