RWD44U Controller Installation and Commissioning Guide 

Document Number 129-408 

 

October 5, 2009

 

Siemens Industry, Inc. 

Page 3 of 10

 

Display Explanation 

Symbol

 

Description 

Setting Range 

 

Symbol

 

Description 

Setting Range 

Main Screen 

 

Adjustable setting screen  

 

 

TOOL 

PC communication port  

being used 

 

#

10 

Application No 

10 through 39 

 

OUT RANGE  The setting is out of range 

 



Day time operation 

 

 

Err 

Sensor error 

 

 

Night time operation 

 

 

Sec 

Seconds 

 

X1 

Universal (Main) Input X1 

Ni 1000 

: -58°F to 302°F  

(-50°C to 150°C) 

(unchangeable) 

Pt 1000 

: -4°F to 356°F  

(-20°C to 180°C) 

(unchangeable) 

0 to 10 Vdc: -100 to 2400 

 

X2 

Universal (Auxiliary) Input  

Ni 1000 

: -58°F to 

302°F (-50°C to 150°C) 

(unchangeable) 

Pt 1000 

: -4°F to 356°F 

(-20°C to 180°C) 

(unchangeable) 

0 Vdc to 10 Vdc: -100 to 

2400 

Variable resistor: The 

resistance range should 

be within 0 

 to 1000 

 

°C 

Celsius scale 

 

 

 

Cooling 

 

°F 

Fahrenheit scale 

 

 

 

Heating 

 

Kelvin 

 

 

SP-h 

Setpoint on the heating side 

for temperature control 

 

Q

 

Digital outputs 

 

 

SP-c 

Setpoint on the cooling side 

for temperature control 

 

R/V 

Reversing valve status = On   

 

 

Output status = Off 

 

 

Standby mode 

 

 

 

Output status = On 

 

"OFF" 

Controller = Off 

 

 

 

 

 

"ON" 

Controller = on standby 

 

 

 

 

 

PS 4 – Differentials and Delays 

SD 

Switching Differential 

0.1 K to 50 K 

  TD 

Time Delay from heat 

 

cool 

0 to 4,096 sec 

T

ON

 

Minimum switch on time 

for Q 

0 to 4,096 sec 

  TD 

Time Delay for next 

stage ON 

0 to 4,096 sec 

T

O

FF 

Minimum switch off time 

for Q 

0 to 4,096 sec 

   

 

 

PS 3 - Auxiliary Control Loop Set-up 

 

Setpoint reset shift  

(Start point, End point and  

Shift differential) 

 

 

 

Setpoint reset shift 

(Start point, End point and  

Shift differential) 

 

SUM 

Summer changeover point 

 

 

 

Time delay from Winter 

 

Summer changeover point 

 

WIN 

Winter changeover point 

 

  D1 

Digital input function 

 

PS 2 - Unit, X1 and X2 Sensor Type and Sensing Range Definition 

Unit 

Define unit 

°C or °F 

  ΔX1 

Calibration offset for X1 

(Ni and Pt sensor only) 

-5 K to 5 K or 

-9°F to 9°F 

X1NI 1000 

X1 is Ni 1000 

 temperature 

sensor 

Ni 1000 

: -58°F to 302°F  

(-50°C to 150°C) (unchangeable) 

  ΔX2 

Calibration offset for X2 

(Ni & Pt sensor only) 

-5 K to 5 K or  

-9°F to 9°F 

X2NI 1000 

X2 is Ni 1000 

 temperature 

sensor 

Ni 1000 

: -58°F to 302°F  

(-50°C to 150°C) (unchangeable) 

  X1L 

Start point of the X1 

(for 0 Vdc to 10 Vdc only) 

-100 to 2400 

X1Pt 1000 

X1 is Pt 1000 

 temperature 

sensor 

Pt 1000 

: -4°F to 356°F  

(-20°C to 180°C) (unchangeable) 

  X2L 

Start point of the X2 

(for 0 Vdc to 10 Vdc only) 

-100 to 2400 

X2Pt 1000 

X2 is Pt 1000 

 temperature 

sensor 

Pt 1000 

: -4°F to 356°F 

(-20°C to 180°C) (unchangeable) 

  X1H 

Stop point of the X1 

(for 0 Vdc  to 10 Vdc only) 

-100 to 2400 

X2SP 

Remote setpoint 

0 Vdc to 10 Vdc or  0 to 1000 

    X2H 

Stop point of the X2 

(for 0 Vdc to 10 Vdc only) 

-100 to 2400 

X2Vr 

Variable Resistor 

 to 1000 

 

   

 

 

 

+  

 

 

Содержание RWD44U

Страница 1: ...X1 for the main temperature sensor Universal input X2 for the following auxiliary functions On Off Standby Setpoint reset Remote setting unit Sensor averaging Alarm Winter Summer setpoint changeover Filter alarm Sensor select Digital input D1 for the following digital functions Day night changeover setpoint On Off Standby Alarm Filter alarm The RWD44U controller is intended for either DIN rail mou...

Страница 2: ...mmissioning Example Two stage compressor with reversing valve on heating and two averaging sensors 35 Table 2 Input Configurations X1 X2 and D1 Applications 10 Through 39 X1 X2 D1 Options Filter Alarm Alarm Day Night Standby x0 Standby Main Standby x1 Remote setpoint Main Remote setpoint x2 Alarm Main Alarm x3 Filter alarm Main Filter alarm x4 Setpoint reset Main Setpoint reset x5 Avg X1 X2 Main M...

Страница 3: ...t cool 0 to 4 096 sec TON Minimum switch on time for Q 0 to 4 096 sec TD Time Delay for next stage ON 0 to 4 096 sec TOFF Minimum switch off time for Q 0 to 4 096 sec PS 3 Auxiliary Control Loop Set up Setpoint reset shift Start point End point and Shift differential Setpoint reset shift Start point End point and Shift differential SUM Summer changeover point Time delay from Winter Summer changeov...

Страница 4: ...Siemens software tool See Software Tool Optional Programming Initial Program Settings New Controller There are five levels of parameter setting PS modes PS1 through PS4 and a setpoint mode Each PS has a set of default parameters which can be changed during commissioning When powered the first time the controller will proceed to PS1 with default application 10 See below for commissioning steps PS 1...

Страница 5: ...differential SD for output stage 1 2 and 3 Sensor range 2 F 1 K Enter min On time for output stage 1 2 and 3 0 to 4 096 s 0 s Enter min Off time for output stage 1 2 and 3 0 to 4 096 s 60 s Enter time delay TD for next stage On 0 to 4 096 s 30 s Enter changeover time delay TD heating cooling demand 0 to 4 096 s 120 s Setpoint Mode Range Type Default Enter SP h1 Sensor range 70 F 21 C Enter SP h2 S...

Страница 6: ...entering any of the setpoint displays the setpoint on display can be adjusted by pushing the SEL λ button Increase value by pressing the button or decrease the value by pressing the button When the required value is reached press the SEL λ button to save the new value Time out For setpoint adjustment during normal operation the controller will exit the setting after 20 seconds and return to the ma...

Страница 7: ...ive unless a parameter has been changed Ensure all outputs are disconnected before changing an application Software Tool Optional Commissioning A software tool for the controller application selection and parameter adjustment is available It is a user friendly Windows 95 or later based software tool The software tool has the following functions Adjusting all available parameters Uploading and down...

Страница 8: ...ations 10 Through 19 C1 C2 H1 H2 X1 X2 S1 PC Cooling stage 1 Cooling stage 2 Heating stage 1 Heating stage 2 Room temperature sensor Auxiliary sensor or a digital input Switch or time clock Personal computer optional for set up only Figure 6 Applications 20 Through 39 CR1 CR2 CR3 RV X1 X2 S1 PC Compressor stage 1 Compressor stage 2 Compressor stage 3 Reversing valve relay Main temperature sensor A...

Страница 9: ...e the ARG62 21 single RWD44U WARNING There must be a minimum of 0 31 inches 8 mm distance from terminations to panel enclosures to avoid electric shock Electrical Installation Notes Standard cables can be used for the controller However when mounting in an environment greatly exposed to EMI use only shielded cables The RWD44U is designed for 24 Vac operating voltage Low voltage must comply with th...

Страница 10: ...duct or company names mentioned herein may be the trademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 129 408 Printed in the USA ...