RWD44U/45U/62U/68U/82U Controllers
Application Guide Quick Reference
Document Number 125-3511
March 28, 2005
Table 8. RWD 45U Controller Output Configurations – Digital Outputs Q1, Q2, Q3, Q4, and Y1.
Application
Numbers
Q1 Q2 Q3 Q4
Y1
10 through 19
Eco Cool
40 through 49
Eco Heat
70 through 79
Heating Stage 2 (H2)
Heating Stage 1 (H1)
Cooling Stage 1 (C1)
Cooling Stage 2 (C2)
Ind
Application
Numbers
Q1 Q2 Q3 Q4
Y1
20 through 29
Reversing Valve (RV)
Cool
30 through 39
Reversing Valve (RV)
Heat
Eco Cool
50 through 59
Reversing Valve (RV)
Cool
60 through 69
Reversing Valve (RV)
Heat
Eco Heat
80 through 89
Reversing Valve (RV)
Cool
90 through 99
Reversing Valve (RV)
Heat
Compressor Stage 1
(Cr1)
Compressor Stage 2
(Cr2)
Compressor Stage 3
(Cr3)
Ind
Table 9. RWD62U Controller Application Numbers.
Main Loop
H = Heating
C = Cooling
SP = Setpoint
(First digit =
Main control loop
Second digit = Auxiliary
control loop)
SP
SP
SP SP
SP
SP
Auxiliary Loop
#1 ×
H Sequence
#2 ×
H + H
Sequences
# 3 ×
H + C Sequences
#4 ×
C Sequence
#5 ×
C + C
Sequences
#x0 (No auxiliary)
#10
#20
#30
#40
#50
#x1 (Remote setpoint)
#11
#21
#31
#41
#51
#x2 (Absolute limiter)
#12
#22
#32
#42
#52
#x3 (Relative limiter)
#13
#23
#33
#43
#53
#x4 (Comp. shift)
#14
#24
#34
#44
#54
#x5 (Cascade)
#15
#25
#35
#45
#55
#x6 (Win/Sum Digital)
#16
#26
#36
–
–
#x7 (Win/Sum Analog)
#17
#27
#37
–
–
#x8 (Maximum priority)
–
–
#38
#48
#58
#x9 Main loop (Active input)
#19
#29
#39
#49
#59
NOTES:
1. The heating sequence output is set to Direct Acting (default). This is typically used for normally open valves.
Output can be set to reverse acting by changing the MIN and MAX value.
2. The cooling sequence output is set to Direct Acting (default). This is typically used for normally closed valves.
Output can be set to reverse acting by changing the MIN and MAX value.
Siemens Building Technologies, Inc.