97/106
Siemens
Basic Documentation RVP360
CE1P2546en
Building Technologies
21 Handling
2017-07-24
Basic information about the plant is obtained by pressing
and
.
Meaning:
Number
Plant information
---
Time of day
0
Outside temperature
1
Flow temperature of heating circuit 1
2
Room temperature of heating circuit 1
3
Return temperature
4
D.h.w. temperature B31
5
D.h.w. temperature B32
6
Collector temperature B6
7
Boiler temperature B2
8
Flow temperature of heating circuit 2
9
Room temperature of heating circuit 2
The information selected last is continuously displayed.
21.1.3 Setting levels and access rights
The operating lines are assigned to different levels. Assignment and access are as
follows:
Level
Op. lines
Access
End-user
1 to 50
Press
or
Heating
engineer
51 to 208
Press
and
simultaneously for 3 seconds
Locking level 248
Press
and
simultaneously until
appears; then, press
,
,
and
one
after the other
The end-user can access all analog operating elements. This means that he
can select the operating mode, readjust the room temperature with the knob,
and activate manual control. Also, he is allowed to access operating lines 1
through 50
The heating engineer can access all operating elements and all operating lines
21.2 Commissioning
21.2.1 Installation Instructions
The controller is supplied complete with Installation Instructions covering in detail
installation, wiring and commissioning with function checks and settings. The
instructions address trained specialists. Each operating line has an empty field
where the set value can be entered.
The Installation Instructions together with the plant’s documentation should be
kept in a safe place!
21.2.2 Operating lines
The most important task when a plant is commissioned is to enter the required type
of plant. This input activates all functions and settings required for the selected type
of plant.
All operating lines contain proven and practice-oriented values. The Installation
Instructions show codings and give guide values, comments, etc., where required.
Info values
Setting levels
Access rights
Selecting operating
line "Plant type"
Setting the other
operating lines