Chapter 6
Certification
RUGGEDCOM RSG2488
Installation Guide
44
EMC and Environmental Type Tests
•
IEC 61850-3
General Requirements
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
Section 6.2
EMC and Environmental Type Tests
The RSG2488 has passed the following EMC and environmental tests.
EMC Type Test for IEC 61850-3
NOTE
• In the case of an all fiber port configuration, this product meets all Class 2 requirements. Otherwise,
all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during which disturbance
errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC1613 conformance is Class 2, during which no disturbance
errors will occur.
Test
Description
Test Levels
Severity Levels
Enclosure Contact
± 8 kV
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
± 4 kV at 2.5 and 5 kHz
Note
a
DC Power Ports
AC Power Ports
± 4 kV at 2.5 and 5 kHz
IEC 61000-4-4
Burst (Fast Transient)
Earth Ground Ports
± 4 kV at 5 kHz
Signal Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
4
DC Power Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced (Conducted) RFI
Earth Ground Ports
10 V
3
100 A/m for 3 min
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 3 s
5
Содержание RUGGEDCOM RSG2488
Страница 4: ...RUGGEDCOM RSG2488 Installation Guide iv ...
Страница 10: ...Preface RUGGEDCOM RSG2488 Installation Guide x Customer Support ...
Страница 14: ...Chapter 1 Introduction RUGGEDCOM RSG2488 Installation Guide 4 Description ...
Страница 30: ...Chapter 2 Installing the Device RUGGEDCOM RSG2488 Installation Guide 20 Configuring the Device ...
Страница 46: ...Chapter 4 Technical Specifications RUGGEDCOM RSG2488 Installation Guide 36 Mechanical Specifications ...