Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
AC Power Ports
5 kV
EMC Immunity Type Tests per IEEE 1613
Note
The RS1600F meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss,
while Class 2 requires error-free and interrupted communications.
Description
Test Levels
Enclosure Contact
± 8 kV
ESD
Enclosure Air
± 15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
± 4 kV @ 2.5 kHz
DC Power Ports
± 4 kV
AC Power Ports
± 4 kV
Fast Transient
Earth Ground Ports
± 4 kV
Signal Ports
2.5 kV Common mode @ 1MHz
DC Power Ports
2.5 kV Common and Differential Mode @ 1MHz
Oscillatory
AC Power Ports
2.5 kV Common and Differential Mode @ 1MHz
Signal Ports
5 kV (Failsafe Relay)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kVAC (Failsafe Relay)
DC Power Ports
1.5 kVDC
Dielectric
Strength
AC Power Ports
2 kVAC
Environmental Type Tests
Test
Description
Test Levels
Severity Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60255-21-1
Vibration
Level 2 (2 g
@ 10-150 Hz)
IEC 60255-21-2
Shock
Level 2 (30 g @ 11 ms)
RUGGEDCOM RS1600F
Installation Manual, 01/2021, C79000-G8976-1014-03
29