Room temperature
Your universal controller offers 4 room operating modes.
Each room operating mode are assigned two tempera-
ture setpoints (heating and cooling).
Depending on the selected room operating mode, your
controller switches the setpoints per a time program
(
page 9) or controls continuously to the setpoint for
the selected room operating mode.
The following setpoints are available. The default factory
settings represent the recommended setpoints.
You can change the comfort and precomfort setpoints as
needed. The economy setpoint cannot be set at the user
level.
Symbol
Setpoint
Impact on the room?
Guide value
Room operating
mode
Heating
Cooling
Comfort
This is the setpoint for the occupied room.
Ensuring comfortable conditions
21 °C
24 °C
Precomfort
This is the energy saving setpoint for the room to ensure that com-
fortable conditions are reached quickly when changing to comfort
mode
19 °C
28 °C
Economy
Plant OFF. A maximum / minimum temperature is ensured in the
room (sustained mode)
15 °C
30 °C
Protection
Plant OFF. Frost protection active
----
----
Path:
Welcome > Main menu > Controller 1... > ...
Содержание RMU7 B Series
Страница 2: ......
Страница 3: ...74 319 0350 0 B3144x2 Synco 700 de Bedienungsanleitung Universalregler RMU7 B 74 319 0350 0 ...
Страница 25: ...74 319 0350 0 B3144x2 Synco 700 en Operating Instructions Universal Controllers RMU7 B 74 319 0350 0 ...
Страница 47: ...74 319 0350 0 B3144x2 Synco 700 fr Manuel d utilisation Régulateur universel RMU7 B 74 319 0350 0 ...
Страница 69: ...74 319 0350 0 B3144x2 Synco 700 nl Gebruiksaanwijzing Universele regelaar RMU7 B 74 319 0350 0 ...