background image

Technical Instructions 

RDU20U, RDU50U and RDU50.2U Room Temperature Controllers 

Document Number 155-735 

with LCD for Heating and Cooling Systems 

November 1, 2006 

Page 4 

 

Siemens Industry, Inc. 

 

Inversion of Output 
Signal  

RU50U and RDU50.2U 

The output signal can be inverted with the help of DIP Switch No. 2. If set to ON, 0V 
corresponds to 0% travel and 10V to 100% travel (reverse acting heating/reverse acting 
cooling). In the OFF position, 0V corresponds to 100% travel and 10V to 0% travel 
(direct acting heating/direct acting cooling). See Figure 7 and Figure 8 for control 
characteristics. 

Heating-Cooling with 
Minimum Limitation 
Cooling 

RU50U and RDU50.2U 

 

Figure 7.  Reverse Acting Heating/ 

Reverse Acting Cooling Function 

Diagram. 

 

Figure 8.  Direct Acting Heating/Direct 

Acting Cooling Function Diagram. 

 

Room temperature 

Y

Out

  Output percentage 

Room temperature setpoint 

XpH  Proportional band heating 

XpK  Proportional band cooling 
VR 

0% to 100% minimum limitation of 

 

cooling output 

c/o 

Changeover 

Minimum Limitation of 
Cooling Signal 

Using parameter P11, the cooling signal output can be limited to a minimum value 
between 0 and 100% (0 to 10 Vdc). This can be used to ensure a minimum supply air 
volume. When used in connection with a VAV controller, this setting must be taken into 
account. See VR in Figure 7 and Figure 8. 

Return Air Temperature 

The RDU Controllers provide control depending on either the measured room 
temperature or the return air temperature. The return air temperature measurement 
overrides the internal measurement automatically if a QAH11.1 cable temperature 
sensor is connected to input 4

–3 (RDU50U and RDU50.2U) or 8–9 (RDU20U). 

Parameter P12 shows which temperature sensor is currently active. 

Display 
(See Table 5) 

  The settings for Parameters P12, P13, and P14 cannot be changed; they are for 

displaying information settings only. 

  The RDU50.2U Controller does not have a parameter setting or display for 

Parameter P14. 

  Parameter P14 (RDU20U and RDU50U) displays the current heat/cool changeover 

temperature 32°F to 120°F (0°C to 49°C), and  
100 = Input open or no sensor connected

–Heating mode 

00 = Input bridged

–Cooling mode. 

  For Parameter P12: 

01 = The room temperature sensor is active. 
02 = The return air temperature sensor is active. 

  Parameter P13 displays the current room temperature 32°F to 120°F (0°C to 49°C). 

Operating Modes 

Normal Mode 

 

Heating or cooling mode with automatic changeover. The controller maintains the 
adjusted setpoint in normal operation. 

Содержание RDU20U

Страница 1: ...ng changeover RDU20U and RDU50U Manual heating cooling changeover RDU50 2U Operating modes Normal Energy Saving and Off Operating mode changeover input for remote control Selectable installation and control parameters Adjustable minimum limitation for cooling output Optional selectable Direct Acting or Reverse Acting output Selectable display of room temperature or setpoint Fahrenheit or Celsius s...

Страница 2: ... damper actuators 155 187P25 All Models Powermite MZ Series Two way globe zone valves 155 198P25 Powermite MZ Series Three way globe zone valves 155 199P25 Powermite MT Series Two way globe zone valves 155 196P25 Powermite MT Series Three way globe zone valves 155 197P25 Powermite 599 Series Two way ball valves 155 704P25 Function The controller measures the room temperature with its integrated se...

Страница 3: ... is used by the controller to switch from heating to cooling mode or vice versa When the water temperature is above 82 F 28 C the controller switches to Heating mode below 61 F 16 C it switches to Cooling mode If immediately after switching on the temperature is between the two changeover points the controller will start in Heating mode The medium temperature is measured at half minute intervals a...

Страница 4: ...to 10 Vdc This can be used to ensure a minimum supply air volume When used in connection with a VAV controller this setting must be taken into account See VR in Figure 7 and Figure 8 Return Air Temperature The RDU Controllers provide control depending on either the measured room temperature or the return air temperature The return air temperature measurement overrides the internal measurement auto...

Страница 5: ...nical Design The unit consists of two parts Plastic housing accommodates the electronics the operating elements and the built in room temperature sensor Base plate houses the wire terminations The housing engages in the controller base and is secured with two screws The screw terminals are mounted on the base plate The DIP switches are located on the circuit board which is accessible through the r...

Страница 6: ...set during operation without opening the unit A 24 Vac supply to the controller is required to enable parameter adjustment The parameters can be changed as follows 1 Press buttons and simultaneously for a minimum of three seconds and a maximum of five seconds Release the buttons and then press button again for approximately three seconds until the display shows P01 2 Select the required parameter ...

Страница 7: ...o 4 K 1 Kelvin 2 F in increments of 1 F 0 5 K 2K P08 P band in heating mode switching differential when ON OFF output is selected RDU20U 0 5 K to 4 K 1 Kelvin 2 F in increments of 1 F 0 5 K 2K P09 P band in cooling mode RDU20 when ON OFF output selected 0 5 K to 4 K 1 Kelvin 2 F in increments of 1 F 0 5 K 1K P10 Integration time 1 to 10 min in increments of 1 min 5 minutes P11 Minimum output limit...

Страница 8: ... is then ready to operate Mount the unit on a wall of the room to be heated or cooled Do not mount in direct sunlight or near other heat or refrigeration sources See Figure 11 Mounting height is approximately 60 inches 150 cm above the floor See Figure 11 The connecting wires can be run to the controller from a recessed conduit box Figure 11 Acceptable Mounting Locations Prior to fitting the chang...

Страница 9: ... and D1 Operational data Setpoint setting range 41 F to 95 F 5 C to 35 C Control deviation at 77 F 25 C Maximum 1 6 F 0 9 C P band in heating mode adjustable in 0 5K increments 1 Kelvin 2 F 0 5K to 4K Factory setting 2K P band in cooling mode adjustable in 0 5K increments 1 Kelvin 2 F 0 5K to 4K Factory setting 1K Integral action time adjustable 1 to 10 minutes Factory setting 5 minutes Setpoint E...

Страница 10: ... Operating voltage 24 Vac negative 2 Operating voltage 24 Vac positive 3 Operating voltage 24 Vac positive 4 Control signal opening 24 Vac 6 Control signal closing 24 Vac 7 Changeover heat cool input 8 Measuring neutral sensors 9 Remote temperature sensor D1 Signal input for potential free GND operating mode changeover Figure 13 RDU20U Wiring Diagram Figure 14 RDU50U Wiring Diagram Figure 15 RDU50...

Отзывы: