The terminal protocol should be set to

XL Graphics

 or

 MXL VDT 132

 if super-

vision to the terminal (Port A) is re-
quired during monitoring. Otherwise, set
it to

 No Device

 if this port is going to be

used for programming only.

(7) - (A)

This setting should match the communi-

cation parameter of the device to which
this port connects.

The terminal settings can be left at the factory
defaults (indicated above) to allow for connection
of a VDT Terminal or PC for programming
purposes.

NOTE:

  When the MXL-VDT is connected to Port

A of the RDM-MXL and its supervision is
required, the MXL communication
parameters 

must

 match the terminal

communication parameters.

(4) Dialup Communication Setup

(1)

The

 Setup String

 is for modem com-

munication and it should not be
changed from the factory default
(indicated above).

(2)

Dialing is normally set to TONE, but
PULSE dialing can be set if required by
the telephone exchange.

(3) - (6)

The communications parameters for

Dialup Connections between RDM-MXL
and RDM-PC should not be changed
unless explicitly required.

(7)

Show Diagnostics

 is a special mode

which should only be activated by
technicians in order to resolve modem
communication problems at installa-
tion. The default setting is set to

 NO.

(5) Dialup Logins

Options (1) to (4) are required for each Login Name.

(1)

Login:

   Name which will be used to

identify who is calling in from RDM-PC.
Login names 

must

 be unique for each

entry.

(2)

Phone Number:

  The telephone

number which the RDM-MXL will use
to call back to connect to the RDM-PC.

(3)

Password:

  Once the RDM-MXL has

called  back the RDM-PC, this pass-
word is used for additional security. It
is also used to identify the person
logging on (using the MENU option
during programming the RDM-MXL).

(4)

Dialup Allowed:

  Setting this option to

Yes

 allows the RDM-MXL to dial out to

a remote location. Setting this option to

No

 disables the RDM-MXL from dialing

back. Use the

 NO

 setting to temporarily

Содержание RDM-MXL

Страница 1: ... a W t a l F 1 L X M M D R r o f r o t c e n n o c r e w o P 1 L X M M D R r o f r o t c e n n o c y a l e r n o i s i v r e p u S 1 l e b a l l a v o r p p a C C F l a n o i t i d d A The user will need to supply the following items Y T I T N A U Q M E T I 1 r o f 1 M D R o t y r e t t a B d n a L X M m o r f e l b a C 1 M I P L X M 1 r o f 1 M D R o t 1 M I P m o r f e l b a C e c a f r e t n I ...

Страница 2: ...ter plate for the MOM 4 position This bracket has the same footprint as the MOM 4 and can accommodate 2 RMD MXL modules An assembly kit is included with the bracket that contains four nuts and eight screws Mount the bracket in the enclosure with four nuts at the positions labeled X in Figure 2 Refer to Figure 3 for wiring in the MXL MXLV enclosure The RDM MXL can also mount to a SYS3 MPFO adaptor ...

Страница 3: ...3 Figure 3 Wiring the RDM MXL in an MBR 2 or MME 3 Enclosure ...

Страница 4: ...4 Figure 4 Connecting the RDM MXL to the MXL MXL IQ System with MMB 2 SMB 2 Main Board Figure 5 Connecting the RDM MXL to the MXL MXL IQ System with MMB 1 SMB 1 Main Board ...

Страница 5: ... MXL an additional adhesive label has been supplied In the case of the MXL Fire Indicator Panel this can be affixed to the door of the MXL cabinet 3 This equipment complies with Part 68 and Part 15 of the FCC rules On the back of the RDM MXL is a label that contains among other information the FCC registration number and ringer equivalence number REN If requested this information must be supplied ...

Страница 6: ...ing MENU you will be prompted to enter a login password before you can configure the RDM MXL This password corresponds to the password configured for your login name The RDM MXL is shipped with the highest level level 1 password of PWORD1 After entering the correct password the main menu will scroll on the screen entering the incorrect password will exit the programming mode and revert the RDM MXL...

Страница 7: ...cted supervision failure on Port A will transfer the supervision relays and will annunciate a Printer Offline trouble in condition on the MXL When failure occurs the RDM will get no further events from the MXL Relay Rating 30V 1A resistive 125 VAC 0 250A resistive Please note that the relays are not set to fail safe mode Both relays will energize when supervision failure is detected on any supervi...

Страница 8: ... can be set if required by the telephone exchange 3 6 The communications parameters for Dialup Connections between RDM MXL and RDM PC should not be changed unless explicitly required 7 Show Diagnostics is a special mode which should only be activated by technicians in order to resolve modem communication problems at installa tion The default setting is set to NO 5 Dialup Logins Options 1 to 4 are ...

Страница 9: ...alence number REN If requested this information must be supplied to the telephone company The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of RENs should not exceed 5 To be certain of the number of devices that...

Страница 10: ... be coordinated by a representative designated by the supplier Any repairs or alterations made by the user to this equipment or equipment malfunctions may give the telecommunications company cause to request the user disconnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metallic water pipe syst...

Страница 11: ...11 ...

Страница 12: ...P N315 096325 4 Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Building Technologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: