7
• To back out of a menu (and return to the Main
Menu) without saving any changes that were
made, press the <
Esc
> key or the
(q)
key.
• The Main Menu is displayed after you type the
correct password from the programming
terminal or PC.
• All Menu options show the factory default for
each setting.
Main Menu
(1)
Sitename
This is displayed to identify the site to which you
are connected. A maximum of 16 characters can
be entered.
(2) Supervision Trouble
This option selects how the monitoring port (Port
A) is supervised if a supervised device such as
the MXL-VDT is installed at this port.
Relay Only:
When this option is selected,
supervision failure on Port A will transfer the
supervision relays but will not annunciate a
trouble condition on the MXL. This is the
default setting.
Software:
When this option is selected,
supervision failure on Port A will transfer the
supervision relays and will annunciate a
Printer Offline
trouble-in condition on the
MXL. When failure occurs, the RDM will get
no further events from the MXL.
Relay Rating:
30V, 1A (resistive)
125 VAC, 0.250A (resistive)
Please note that the relays are not set to fail-safe
mode. Both relays will energize when supervision
failure is detected on any supervised ports or on
modem failure.
(3) RDM-MXL Communication Setup
Options 1-5 set the RDM-1 communication
parameters for MXL communication.
Options 6-A set the RDM-1 communication
parameters for terminal programming and moni-
toring port.
NOTE: BE SURE TO CHECK THE TERMINAL
PROTOCOL SETTING.
(1)
For proper MXL supervision, the MXL
protocol should be set for
MXL VDT
132.
This must also be set in CSG-M
for the PIM-1 port. If
No Device
is
selected, the RDM will not be
supervised by the MXL.
(2) - (5)
For proper communication, set the
MXL communication parameters the
same as the CSG-M settings for the
PIM-1 module.