Operation of LEDs:
Each port has a green and a yellow LED. When
the green LED is lit, it means the port is operat-
ing normally. When the yellow LED is lit, it
means that the port is not operating properly or
there has been supervision failure on this port. If
both LEDs are off, then this port has been
disabled, is not in use, or is not supervised (For
example, Programming port).
• Port A (Programming and Monitoring Ter-
minal port) and Port C (Connection to MXL):
Green LED indicates supervision is all right.
Yellow LED indicates supervision failure
• Port M (modem):
Green LED indicates modem has
established communication and is
operating properly.
Yellow LED indicates modem failure.
CONFIGURATION OF RDM-1 FOR
MXL PIM-1
1. Power up the RDM-MXL. After approximately
3 seconds, all LEDs on the RDM will turn on.
This allows for programming of the RDM-MXL
using the default configuration. The default
configuration requires that a laptop be
connected to port 232-A using a straight-
through RS-232 cable. A terminal program
such as Procom/Telix or Windows Terminal
using VT100 emulation, can be used with
communication parameters set to 9600, 8, N, 1.
2. If MXL-VDT is being used, set the emulation
to VT100 with communication parameters set
to 9600, 8, N, 1. After programming the
RDM-MXL, reset its emulation and
communication parameters to its previous
setting.
3. Type
MENU
while all the LEDs are turned on
to start the RDM menu. There is no need to
press <Enter>.
4.
This is the only time the RDM-1
programming menu can be accessed.
After entering MENU, you will be prompted to
enter a login password before you can
configure the RDM-MXL. This password
corresponds to the password configured for
your login name. The RDM-MXL is shipped
with the highest level (level 1) password of
PWORD1
. After entering the correct
password, the main menu will scroll on the
screen (entering the incorrect password will
exit the programming mode and revert the
RDM-MXL to normal operating mode).
5. Follow the menu options to set the following
information:
Site Name:
The location of the MXL fire
alarm panel.
Supervision:
This option is used to select
how the RDM-MXL supervises its serial
ports. If the supervision relay is not
connected, then SOFTWARE supervision
can be selected. This selection will allow the
MXL to annunciate a supervision failure.
RDM-MXL Communications Setup:
This
submenu sets the communication parameters
to the MXL (Port C) and the monitoring port
(Port A). Make sure that the Port C settings
are the same as the PIM settings in CSG-M.
Also note that for proper supervision, the PIM
should be set for MXL VDT-132.
Dialup Communications Setup
: This
submenu selects the settings for the modem
interface between RDM-MXL and RDM-PC.
Dialup Logins
: This submenu selects the
LOGIN, the telephone number the RDM-MXL
will call and the password it will verify. Up to
8 different login names can be configured.
Menu Options
• Press the key in brackets to select a
particular menu option (For example, press
<
1
> to select option 1).
• When entering in letters (For example, the
Sitename or Login name), press the <
Enter
>
key when finished to save the entry.
• Most other options use the <
SPACE BAR
> to
step through each available setting for that
option (For example, Baud Rate 1200, 2400,
4800, 9600, 19200).