Operation of LEDs:

Each port has a green and a yellow LED. When
the green LED is lit, it means the port is operat-
ing normally. When the yellow LED is lit, it
means that the port is not operating properly or
there has been supervision failure on this port. If
both LEDs are off, then this port has been
disabled, is not in use, or is not supervised (For
example, Programming port).

• Port A (Programming and Monitoring Ter-

minal port) and Port C (Connection to MXL):
Green LED indicates supervision is all right.
Yellow LED indicates supervision failure

• Port M (modem):

Green LED indicates modem has

established communication and is
operating properly.

Yellow LED indicates modem failure.

CONFIGURATION OF RDM-1 FOR
MXL PIM-1

1. Power up the RDM-MXL. After approximately

3 seconds, all LEDs on the RDM will turn on.
This allows for programming of the RDM-MXL
using the default configuration. The default
configuration requires that a laptop be
connected to port 232-A using a straight-
through RS-232 cable. A terminal program
such as Procom/Telix or Windows Terminal
using VT100 emulation, can be used with
communication parameters set to 9600, 8, N, 1.

2. If MXL-VDT is being used, set the emulation

to VT100 with communication parameters set
to 9600, 8, N, 1. After programming the
RDM-MXL, reset its emulation and
communication parameters to its previous
setting.

3. Type 

MENU

 while all the LEDs are turned on

to start the RDM menu. There is no need to
press <Enter>.

4.

This is the only time the RDM-1
programming menu can be accessed.

After entering MENU, you will be prompted to
enter a login password before you can
configure the RDM-MXL. This password

corresponds to the password configured for
your login name. The RDM-MXL is shipped
with the highest level (level 1) password of

PWORD1

. After entering the correct

password, the main menu will scroll on the
screen (entering the incorrect password will
exit the programming mode and revert the
RDM-MXL to normal operating mode).

5. Follow the menu options to set the following

information:

Site Name:

  The location of the MXL fire

alarm panel.

Supervision: 

 This option is used to select

how the RDM-MXL supervises its serial
ports. If the supervision relay is not
connected, then SOFTWARE supervision
can be selected. This selection will allow the
MXL to annunciate a supervision failure.

RDM-MXL Communications Setup:

  This

submenu sets the communication parameters
to the MXL (Port C) and the monitoring port
(Port A). Make sure that the Port C settings
are the same as the PIM settings in CSG-M.
Also note that for proper supervision, the PIM
should be set for MXL VDT-132.

Dialup Communications Setup

:  This

submenu selects the settings for the modem
interface between RDM-MXL and RDM-PC.

Dialup Logins

: This submenu selects the

LOGIN, the telephone number the RDM-MXL
will call and the password it will verify. Up to
8 different login names can be configured.

Menu Options

• Press the key in brackets to select a

particular menu option (For example, press
<

1

> to select option 1).

• When entering in letters (For example, the

Sitename or Login name), press the <

Enter

>

key when finished to save the entry.

• Most other options use the <

SPACE BAR

> to

step through each available setting for that
option (For example, Baud Rate 1200, 2400,
4800, 9600, 19200).

Содержание RDM-MXL

Страница 1: ... a W t a l F 1 L X M M D R r o f r o t c e n n o c r e w o P 1 L X M M D R r o f r o t c e n n o c y a l e r n o i s i v r e p u S 1 l e b a l l a v o r p p a C C F l a n o i t i d d A The user will need to supply the following items Y T I T N A U Q M E T I 1 r o f 1 M D R o t y r e t t a B d n a L X M m o r f e l b a C 1 M I P L X M 1 r o f 1 M D R o t 1 M I P m o r f e l b a C e c a f r e t n I ...

Страница 2: ...ter plate for the MOM 4 position This bracket has the same footprint as the MOM 4 and can accommodate 2 RMD MXL modules An assembly kit is included with the bracket that contains four nuts and eight screws Mount the bracket in the enclosure with four nuts at the positions labeled X in Figure 2 Refer to Figure 3 for wiring in the MXL MXLV enclosure The RDM MXL can also mount to a SYS3 MPFO adaptor ...

Страница 3: ...3 Figure 3 Wiring the RDM MXL in an MBR 2 or MME 3 Enclosure ...

Страница 4: ...4 Figure 4 Connecting the RDM MXL to the MXL MXL IQ System with MMB 2 SMB 2 Main Board Figure 5 Connecting the RDM MXL to the MXL MXL IQ System with MMB 1 SMB 1 Main Board ...

Страница 5: ... MXL an additional adhesive label has been supplied In the case of the MXL Fire Indicator Panel this can be affixed to the door of the MXL cabinet 3 This equipment complies with Part 68 and Part 15 of the FCC rules On the back of the RDM MXL is a label that contains among other information the FCC registration number and ringer equivalence number REN If requested this information must be supplied ...

Страница 6: ...ing MENU you will be prompted to enter a login password before you can configure the RDM MXL This password corresponds to the password configured for your login name The RDM MXL is shipped with the highest level level 1 password of PWORD1 After entering the correct password the main menu will scroll on the screen entering the incorrect password will exit the programming mode and revert the RDM MXL...

Страница 7: ...cted supervision failure on Port A will transfer the supervision relays and will annunciate a Printer Offline trouble in condition on the MXL When failure occurs the RDM will get no further events from the MXL Relay Rating 30V 1A resistive 125 VAC 0 250A resistive Please note that the relays are not set to fail safe mode Both relays will energize when supervision failure is detected on any supervi...

Страница 8: ... can be set if required by the telephone exchange 3 6 The communications parameters for Dialup Connections between RDM MXL and RDM PC should not be changed unless explicitly required 7 Show Diagnostics is a special mode which should only be activated by technicians in order to resolve modem communication problems at installa tion The default setting is set to NO 5 Dialup Logins Options 1 to 4 are ...

Страница 9: ...alence number REN If requested this information must be supplied to the telephone company The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of RENs should not exceed 5 To be certain of the number of devices that...

Страница 10: ... be coordinated by a representative designated by the supplier Any repairs or alterations made by the user to this equipment or equipment malfunctions may give the telecommunications company cause to request the user disconnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metallic water pipe syst...

Страница 11: ...11 ...

Страница 12: ...P N315 096325 4 Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Building Technologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: