The control parameters of the controller can be set to ensure optimum
performance of the entire system (see “Set control parameters”).
·
The control sequence may need to be set via parameter P01 depending on the
application. The factory setting for the 2-pipe application is “Cooling only”; and
“Heating and Cooling” for the 4-pipe application
·
When the controller is used with a compressor, the minimum output on-time
(parameter P48) and off-time (parameter P49) for Y11/Y21 must be adjusted to
avoid damaging the compressor and shortening its life
·
Recalibrate the temperature sensor if the room temperature displayed on the
controller does not match the room temperature measured. To do this, change
parameter P05
·
We recommend to review the setpoints and setpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy
5.2
Operating Instructions
See the operating instructions B3076... enclosed with the controller.
5.3
Disposal
The device is considered electrical and electronic equipment for disposal in terms
of the applicable European Directive and may not be disposed of as domestic
garbage.
·
Dispose of the device through channels provided for this purpose.
·
Comply with all local and currently applicable laws and regulations.
Control sequence
Compressor-based
application
Calibrate sensor
Setpoint and range
limitation