12/14
Siemens
Room Temperature Controllers
N3057en
Building Technologies
2014-10-28
Switching differential, adjustable from 0.5..4 K
Heating mode (factory setting)
Cooling mode (factory setting)
2 K
1 K
Setpoint setting range
Normal operation
Economy (Energy saving) (only with RDF110)
Protection (Standby)
5...40 °C
OFF, 5...40 °C
OFF, 5...40 °C
Factory setting of setpoints
Normal operation
Economy (Energy saving) in heating / cooling
mode
Protection (Standby) (heating and cooling mode)
20 °C
16 °C / 28 °C
OFF
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
0…49 °C
< ± 0.5 K
± 3.0 K
Resolution of settings and display
Setpoints
Current temperature value displayed
0.5 °C
0.5 °C
Operation
Climatic conditions
Temperature
Humidity
to IEC 60721-3-3
class 3K5
0...+50 °C
<95 % r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
to IEC 60721-3-2
class 2K3
−
25...+60 °C
<95 % r.h.
class 2M2
Storage
Climatic conditions
Temperature
Humidity
to IEC 60721-3-1
class 1K3
−
25...+60 °C
<95 % r.h.
EU Conformity (CE)
CE1T3057xx
*)
RCM Conformity
CE1T3057en_C1
*)
Devices of safety class
II to EN 60730-1
Pollution class
normal
Degree of protection of housing
IP 30 to EN 60 529
Connection terminals
solid wires or prepared
stranded wires
2 x 0.4-1.5 mm
2
or 1 x 2.5
mm
2
Weight
0.28 kg
Color of housing front
white, NCS S 0502-G
(RAL 9003)
*) The documents can be downloaded from
http://siemens.com/bt/download
.
Operational data
Environmental
conditions
Norms and standards
General