The following DHW operating modes can be selected: 

Continuously ON:  

Symbol 

 appears on the display 

Continuously OFF:  

No symbol on the display 

Auto:  

 Symbol 

 appears on the display, DHW is switched  

 

   

according to the selected switching pattern 

 
Factory setting: Time switch for DHW 

Day(s) 

DHW control ON  

 

DHW control OFF 

Mo (1) – Fr (5) 

6:00 – 8:00 h and 
17:00 – 22:00 h 

22:00 – 6:00 h and 
08:00 – 17:00 h 

Sa (6) – Su (7) 

7:00 – 22:00 h 

22:00 – 7:00 h 

 

Display 

The digital display shows the actual room temperature, the time of day, the weekday, 
the current switching pattern for heating, the switching pattern for DHW, and the symbol 
of the operating mode currently active. When the heating output is activated, the trian-
gle symbol appears. 

Display of the switching pattern is split up in upper and lower row. 

When the segment is displayed and flashing, the DHW output is activated. When no 
segment is displayed, the DHW output is deactivated. 

Upper row with  
switching pattern  
for DHW control 

 

3/8 

Building Technologies 

Room temperature controller RDE10.1DHW 

CE1N3038en 

0

6

24

12

18

C

 

0

6

24

12

18

C

 

0

6

24

12

18

C

 

    DHW Auto mode 

    DHW ON mode 

    DHW OFF mode 

 

Lower row with  
switching pattern  
for heating  

When the segment is displayed and flashing, the normal temperature setpoint is active. 
When no segment is displayed, the energy saving or frost protection temperature set-
point is active. 
 

0

6

24

12

18

C

 

C

0

6

24

12

18

 

0

6

24

12

18

C

 

    Automatic changeover 

    Normal operation 

    Energy saving mode 

    according to switching pattern 

 

OFF mode and frost 
protection display 

0

6

24

12

18

C

 

0

6

24

12

18

C

 

    OFF mode 

    Frost protection mode 

 

Backup 

When taking out the batteries, the setpoints and the information required for operating 
mode changeover are memorized. However, the real time clock must be reset after the 
batteries are replaced.  
 
 

HVAC Products 

 

20.10.2005 

Содержание RDE10.1DHW

Страница 1: ...h and manual control Battery powered DC 3 V 2 x 1 5 V AA Use The RDE10 1DHW is used for the control of the room temperature in heating systems with independent control of DHW Typical applications Residential apartments For the control of the following plant components and of DHW Thermal valves or zone valves Gas or oil burners Fans Pumps Heat exchanger Continuous flow water heater Small water heat...

Страница 2: ... then keeping button depressed for 4 seconds In that case symbol does not appear When frost protection mode is activated symbol appears on the display Frost protection 7 day time switch The changeover between normal and energy saving temperature setpoints can take place either automatically or manually depending on the selection of the operating mode When pressing the operating mode button until a...

Страница 3: ... and flashing the DHW output is activated When no segment is displayed the DHW output is deactivated Upper row with switching pattern for DHW control 3 8 Building Technologies Room temperature controller RDE10 1DHW CE1N3038en 0 6 24 12 18 C 0 6 24 12 18 C 0 6 24 12 18 C DHW Auto mode DHW ON mode DHW OFF mode Lower row with switching pattern for heating When the segment is displayed and flashing th...

Страница 4: ...30 mm ARG70 2 Mechanical design The controller consists of 2 parts Plastic housing with digital display which accommodates the electronics the oper ating elements and the built in room temperature sensor Mounting base The housing engages in the mounting base and snaps on The base carries the screw terminals 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 19 17 18 16 20 3038Z05 1 Display of the room temperatur...

Страница 5: ...r can be fitted to a recessed conduit box Only authorized staff may open the unit Caution AC 230 V The cables used must satisfy the insulation requirements with regard to mains potential Mounting installa tions and commis sioning When mounting the controller fix the base first Then make the electrical connections and fit and secure the cover also refer to the relevant Mounting Instructions The con...

Страница 6: ...nergy saving 0 OFF and 5 35 C Factory setting normal operation 20 C Factory setting energy saving 8 C Frost protection 5 C fixed Resolution of settings and displays Setpoints 0 5 C Switching times 60 min Actual temperature value displays 0 5 C Time of day displays 1 min Operational data Operation to IEC 721 3 3 Climatic conditions class 3K5 Temperature 0 50 C Humidity 95 r h Transport to IEC 721 3...

Страница 7: ... Q22 Q24 inverse of Q24 3038A02 3V Lx Nx AC 24 250 V max 5 2 A Legend Y1 Heating valve or wall hung boiler Y2 DHW heating equipment Application examples T T F1 F2 N1 M1 Y2 3033S01 T DHW T F1 F2 N1 M1 Y2 3033S02 T T DHW Room temperature controller with direct control of a gas fired wall hung boiler and independent control of DHW Room temperature controller with direct control of a gas fired floor s...

Страница 8: ...ith manual adjustment Magnetic valve DHW heating equipment Room temperature controller with direct control of a heating circuit pump precontrol by manual mixing valve and independent control of DHW Dimensions Controller and base 8 8 Building Technologies Room temperature controller RDE10 1DHW CE1N3038en 2005 Siemens Switzerland Ltd Subject to alteration HVAC Products 20 10 2005 ...

Отзывы: