Technical Instructions 

QVM62.1 Air Velocity Sensor 

Document Number 155-006 
October 26, 2006 

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as 
design improvements are introduced. © 2006 Siemens Industry, Inc. 

 

Siemens Industry, Inc. 

Building Technologies Division 
1000 Deerfield Parkway 
Buffalo Grove, IL 60089 
+ 1 847-215-1000 

Your feedback is important to us. If you have 
comments about this document, please send them 
tDocument No. 155-006 

Printed in the USA 

Page 4 

 

 

Mounting and 
Installation Notes 

Mount the immersion stem so that the air flows through the opening at the sensor head.  

The immersion stem is pre-mounted and wired to the transducer on delivery. The 
sensor pipes and the end with the direction arrow are prearranged on the connecting 
cable; fit them together (use the direction-oriented snap-on connections). If the 
extension pipe is not required, remove it from the cable. The connecting flange is not 
attached on delivery. 

The sensor is supplied with Installation Instructions. 

Commissioning 
Notes 

Check the wiring and air velocity range settings prior to commissioning. 

Check the immersion stem position in the air duct (see

 Installation Instructions

). 

Wiring Diagram 

 

Figure 3.  Wiring Diagram. 

G  24 Vac operating voltage 

M  Measuring neutral/operating voltage 

ground 

U1  0 to 10 Vdc output signal 

Dimensions 

 

 

Figure 4.  Dimensions in Inches (Millimeters). 

 

 

Содержание QVM62.1

Страница 1: ... 0 to 49 ft s 0 to 15 m s The sensor measures a point that is it measures the values at a specific location in the flow profile For recording the mean air velocity in the duct the sensor s immersion depth is the key measure The immersion depth depends on the flow profile The measurement principle is based on the anemometric measurement principle The specially developed thin film sensing element of...

Страница 2: ...erminal block for connection to the immersion stem 2 Terminal block for connection to the controller 3 Plug in unit for setting the three velocity ranges No plug in jumper 0 to 16 ft s 0 to 5 m s Plug in on 1 and 2 0 to 32 ft s 0 to 10 m s Factory setting Plug in on 2 and 3 0 to 49 ft s 0 to 15 m s Specifications Power supply Operating voltage 24 Vac 20 Frequency 50 60 Hz Power consumption 5 VA ma...

Страница 3: ...ss 1M2 Transportation Temperature 23 F to 113 F 5 C to 45 C Humidity non condensing 95 rh Mechanical conditions Class 2M2 Materials and colors Housing bottom Polycarbonate RAL 7001 silver gray Housing cover Polycarbonate RAL 7035 light gray Sensor pipes Polycarbonate RAL 7001 silver gray Sensor head extension enc Polycarbonate RAL 7035 light gray Connecting flange Polycarbonate RAL 7001 silver gra...

Страница 4: ...ersion stem so that the air flows through the opening at the sensor head The immersion stem is pre mounted and wired to the transducer on delivery The sensor pipes and the end with the direction arrow are prearranged on the connecting cable fit them together use the direction oriented snap on connections If the extension pipe is not required remove it from the cable The connecting flange is not at...

Отзывы: