Siemens QVM62.1 Скачать руководство пользователя страница 2

Technical Instructions 

QVM62.1 Air Velocity Sensor 

Document Number 155-006 
October 26, 2006 

Page 2 

 

Siemens Industry, Inc. 

 

Operation 
(Continued) 

A scale with 0.20 in (0.5 cm) grating on the immersion stem and the extension pipe 
indicates the immersion depth. 

The connecting flange is used to attach and seal the immersion stem on the duct wall. 

A plastic housing with removable cover accommodates the transducer. It can be 
screwed to a flat surface. 

The sensor cable is connected: the sensor and the transducer are a unit. 

The measuring ranges are selected by inserting or removing a plug-in jumper. 

Protection against false wiring is provided related to own voltages. (Measuring output 
U1 is short-circuit proof.) The sensor head connections are not protected against 24 
Vac operating voltage. 

Components 

 

Figure 1. Wiring and Setting Elements. 

1 Terminal block for connection to the 

immersion stem. 

2 Terminal block for connection to the 

controller. 

3. Plug-in unit for setting the three velocity 

ranges. 

  No plug-in jumper  = 0 to 16 ft/s  

(0 to 5 m/s) 
Plug-in on 1 and 2  = 0 to 32 ft/s  
(0 to 10 m/s) 
(Factory setting) 
Plug-in on 2 and 3  = 0 to 49 ft/s  
(0 to 15 m/s) 

Specifications 

Power supply 

Operating voltage 

24 Vac +/- 20% 

Frequency 

50/60 Hz 

Power consumption 

< 5 VA (maximum 200 mA) 

Output impedance 

<20 ohm 

Measuring data 

Measuring ranges, adjustable 

0 to 16 ft/s (0 to 5 m/s) 

 

 

 

0 to 33 ft/s (0 to 10 m/s) 

 

 

 

(factory setting) 

 

 

 

0 to 49 ft/s (0 to 15 m/s) 

Measuring accuracy at 68°F (20°C), 45% rh, 

+ 0.7 ft/s (0.2 m/s + 3% of measured 

 

1013 hPa 

value) 

Permissible air velocity 

66 ft/s (20 m/s) 

Direction dependence 

< 0.3% of measured value at< + 10° 

Time constant t

90

 at 10 m/s 

ca. 4 seconds 

Signal output U1 

Voltage  

0 to 10 Vdc 

Current  

+ 1 mA 

Line length 

Permissible length to controller at: 
 

20 AWG copper cable 

164 ft (50 m) 

 

18 AWG copper cable 

492 ft (150 m) 

 

16 AWG copper cable 

984 ft (300 m) 

Line length to the sensor head 

3 ft (1 m) (prewired) 

Содержание QVM62.1

Страница 1: ... 0 to 49 ft s 0 to 15 m s The sensor measures a point that is it measures the values at a specific location in the flow profile For recording the mean air velocity in the duct the sensor s immersion depth is the key measure The immersion depth depends on the flow profile The measurement principle is based on the anemometric measurement principle The specially developed thin film sensing element of...

Страница 2: ...erminal block for connection to the immersion stem 2 Terminal block for connection to the controller 3 Plug in unit for setting the three velocity ranges No plug in jumper 0 to 16 ft s 0 to 5 m s Plug in on 1 and 2 0 to 32 ft s 0 to 10 m s Factory setting Plug in on 2 and 3 0 to 49 ft s 0 to 15 m s Specifications Power supply Operating voltage 24 Vac 20 Frequency 50 60 Hz Power consumption 5 VA ma...

Страница 3: ...ss 1M2 Transportation Temperature 23 F to 113 F 5 C to 45 C Humidity non condensing 95 rh Mechanical conditions Class 2M2 Materials and colors Housing bottom Polycarbonate RAL 7001 silver gray Housing cover Polycarbonate RAL 7035 light gray Sensor pipes Polycarbonate RAL 7001 silver gray Sensor head extension enc Polycarbonate RAL 7035 light gray Connecting flange Polycarbonate RAL 7001 silver gra...

Страница 4: ...ersion stem so that the air flows through the opening at the sensor head The immersion stem is pre mounted and wired to the transducer on delivery The sensor pipes and the end with the direction arrow are prearranged on the connecting cable fit them together use the direction oriented snap on connections If the extension pipe is not required remove it from the cable The connecting flange is not at...

Отзывы: