QVM62.1 Air Velocity Sensor 

Technical Instructions 

 

Document Number 155-006 

 

October 26, 2006 

Siemens Industry, Inc. 

Page 3

 

Connections 

Mechanical 

Screw connection 

Electric  

Screw terminal, maximum 2 × 18 AWG 

Degree of protection 

Degree of protection provided by enclosures 
 

as per EN 60 529 

 

 

Transducer 

IP 42 

 

 

Sensor head 

IP 20 

Degree of protection as per EN 60 730 

III 

Environmental conditions 

Climatic conditions 
 

Temperature 

23°F to 113°F (-5°C to 45°C) 

 

Humidity (non-condensing) 

<95% rh 

Mechanical conditions 

Class 3M2 

Chemical conditions 

Class 3C2 

Storage (transducer and immersion stem) 
 

Temperature 

23°F to 113°F (-5°C to 45°C) 

 

Humidity (non-condensing) 

<95% rh 

 

Mechanical conditions 

Class 1M2 

Transportation 
 

Temperature 

23°F to 113°F (-5°C to 45°C) 

 

Humidity (non-condensing) 

<95% rh 

 

Mechanical conditions 

Class 2M2 

Materials and colors 

Housing bottom 

Polycarbonate, RAL 7001 (silver-gray) 

Housing cover 

Polycarbonate, RAL 7035 (light gray) 

Sensor pipes 

Polycarbonate, RAL 7001 (silver-gray) 

Sensor head, extension, enc 

Polycarbonate, RAL 7035 (light gray) 

Connecting flange 

Polycarbonate, RAL 7001 (silver gray) 

Sensor   

Silicone-free 

Weight 

With packaging 

12 oz (0.352 kg) 

Engineering Notes 

Place the sensor in a location where the airflow is quiet. Do not place it close to 
dampers, registers or duct direction changes. 

 

 

 

 

 

 

Figure 2.  Sensor Placement. 

 

Use a transformer with safety extra-low voltage (SELV) and separate winding for 100% 
ON-time. 

Observe all local safety rules and regulations pertaining to sizing and protecting 
transformers. 

Note the permissible line length to the controller. 

Содержание QVM62.1

Страница 1: ... 0 to 49 ft s 0 to 15 m s The sensor measures a point that is it measures the values at a specific location in the flow profile For recording the mean air velocity in the duct the sensor s immersion depth is the key measure The immersion depth depends on the flow profile The measurement principle is based on the anemometric measurement principle The specially developed thin film sensing element of...

Страница 2: ...erminal block for connection to the immersion stem 2 Terminal block for connection to the controller 3 Plug in unit for setting the three velocity ranges No plug in jumper 0 to 16 ft s 0 to 5 m s Plug in on 1 and 2 0 to 32 ft s 0 to 10 m s Factory setting Plug in on 2 and 3 0 to 49 ft s 0 to 15 m s Specifications Power supply Operating voltage 24 Vac 20 Frequency 50 60 Hz Power consumption 5 VA ma...

Страница 3: ...ss 1M2 Transportation Temperature 23 F to 113 F 5 C to 45 C Humidity non condensing 95 rh Mechanical conditions Class 2M2 Materials and colors Housing bottom Polycarbonate RAL 7001 silver gray Housing cover Polycarbonate RAL 7035 light gray Sensor pipes Polycarbonate RAL 7001 silver gray Sensor head extension enc Polycarbonate RAL 7035 light gray Connecting flange Polycarbonate RAL 7001 silver gra...

Страница 4: ...ersion stem so that the air flows through the opening at the sensor head The immersion stem is pre mounted and wired to the transducer on delivery The sensor pipes and the end with the direction arrow are prearranged on the connecting cable fit them together use the direction oriented snap on connections If the extension pipe is not required remove it from the cable The connecting flange is not at...

Отзывы: