QVM62.1 

Technical Instructions 

Document No. 155-006 

October 26, 2006 

 

Air Velocity Sensor 

 

 

Siemens Industry, Inc. 

Description 

This sensor is used to control the air velocity to a constant value, balance out pressure 
fluctuations (supply or exhaust air control), or to monitor the flow in air ducts. It is 
primarily used for modulating fan control in primary applications to set the basic volume 
flow. 

Application 

The QVM62.1 Sensor records the air velocity as a measured value and converts it to 
an active 0 to 10 Vdc output signal. There are three measuring ranges available:  

  0 to 16 ft/s (0 to 5 m/s) 

  0 to 33 ft/s (0 to 10 m/s) 

  0 to 49 ft/s (0 to 15 m/s). 

The sensor measures a point (that is it measures the values at a specific location in the 
flow profile. For recording the mean air velocity in the duct, the sensor’s immersion 
depth is the key measure. The immersion depth depends on the flow profile.  

The measurement principle is based on the anemometric measurement principle. The 
specially developed thin film sensing element of the QVM62.1 is almost totally 
independent from the flow direction and is insensitive to almost any kind of dirt in the 
airflow. 

Product Number 

QVM62.1 

Operation 

The air velocity sensor consists of: 

  Immersion stem with sensor head and sensing element 

  Extension pipe with fitting 

  Immersion stem end with flow direction arrow 

  Adjustable connecting flange 

  Transducer 

  Connection cable, screened, four-core, 3 feet (1 m) long 

Содержание QVM62.1

Страница 1: ... 0 to 49 ft s 0 to 15 m s The sensor measures a point that is it measures the values at a specific location in the flow profile For recording the mean air velocity in the duct the sensor s immersion depth is the key measure The immersion depth depends on the flow profile The measurement principle is based on the anemometric measurement principle The specially developed thin film sensing element of...

Страница 2: ...erminal block for connection to the immersion stem 2 Terminal block for connection to the controller 3 Plug in unit for setting the three velocity ranges No plug in jumper 0 to 16 ft s 0 to 5 m s Plug in on 1 and 2 0 to 32 ft s 0 to 10 m s Factory setting Plug in on 2 and 3 0 to 49 ft s 0 to 15 m s Specifications Power supply Operating voltage 24 Vac 20 Frequency 50 60 Hz Power consumption 5 VA ma...

Страница 3: ...ss 1M2 Transportation Temperature 23 F to 113 F 5 C to 45 C Humidity non condensing 95 rh Mechanical conditions Class 2M2 Materials and colors Housing bottom Polycarbonate RAL 7001 silver gray Housing cover Polycarbonate RAL 7035 light gray Sensor pipes Polycarbonate RAL 7001 silver gray Sensor head extension enc Polycarbonate RAL 7035 light gray Connecting flange Polycarbonate RAL 7001 silver gra...

Страница 4: ...ersion stem so that the air flows through the opening at the sensor head The immersion stem is pre mounted and wired to the transducer on delivery The sensor pipes and the end with the direction arrow are prearranged on the connecting cable fit them together use the direction oriented snap on connections If the extension pipe is not required remove it from the cable The connecting flange is not at...

Отзывы: