![Siemens QMX3.P02 Скачать руководство пользователя страница 42](http://html.mh-extra.com/html/siemens/qmx3-p02/qmx3-p02_technical-principles_374281042.webp)
42 / 46
Siemens
Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
CM2N1602en_05
Building Technologies
ETS engineering
2018-09-14
5.6 Examples for the operation of touch keys
and display elements
In RTS, these functions are created as follows:
In the device view,
•
activate or deactivate functions
•
modify the default values if required
The objects that are now visible, must be connected to group addresses.
Key 1
Toggle the display between outdoor and indoor temperature
Keys 2 and 6
Room temperature setpoint adjustment (absolute)
Keys 3, 4 and 5
No function (no arrow symbols are displayed)
Key 7
Toggle the room operating mode (in Auto mode, the present operating mode is
displayed)
Key 8
Presence key, or Comfort extension
Key 1
No function, as only room temperature is displayed
Keys 2 and 6
Room temperature setpoint adjustment (relative)
Keys 3 and 7
Manual adjustment of fan speed
Key 4
Toggle the display pages between temperature, humidity, and CO
2
Keys 5 and 8
No function
Temperature and room
operating modes
Temperature,
fan control and
navigation