5.4 Room operator unit visualization and
operation
The appropriate communication objects must be placed
in the group address
after parameterization to display internal functions on the room operator unit.
O
bj
ect
n
o.
Name
Description
Q
M
X3
.P3
4
Q
M
X3
.P7
4
Q
M
X3
.P3
7
1 Room temperature
Displays the value of the internal room temperature sensor
X X X
55 Room temperature,
setpoint absolute
Displays the Comfort setpoint that can be changed on the display.
X X X
56 Room temperature,
setpoint relative
X X X
58 Room operating mode,
preselection
Displays the room operating mode that can be changed on the display (Auto-Comfort-
PreComfort-Eco-Protection).
The
present state
is displayed in AUTO mode (Auto-Comfort-PreComfort-Eco-
Protection).
X X X
17 Comfort mode, timer
button
Object 17 activates comfort extension. The extension period can be configured. OR ...
... Object 63 activates the display and manual entry for occupancy or non-occupancy.
X X X
63 Occupancy: Button
X X X
68 Control mode
(heating/cooling/off)
Displays the symbols for the present control mode.
Off: No symbol is displayed.
X X X
18...21 Window state
Displays the symbol "Open window" (only during active PID control).
X X X
65 Fan, default value (%)
Displays the fan speed that can be changed on the display.
The value can also be received via bus when adjusted on another device.
X X X
66 Fan mode:
(Auto-Manual)
Displays the fan operating mode that can be changed on the display. The value can
also be received via bus when adjusted on another device.
X X X
67 Fan (%)
Displays the actual fan speed as reported to the bus by the actuator/controller.
X X X
25 Room humidity
Provides the value of the internal CO
2
sensor to the bus.
X
38 CO
2
concentration
Provides the value of the internal room humidity sensor to the bus.
X
71 Room humidity:
Setpoint
Displays the Comfort setpoint that can be changed on the display.
X X X
74 CO
2
concentration:
Setpoint
Displays the CO
2
setpoint that can be changed on the display.
X X X
Other important group addresses for operation and display on room operator units via
communication objects:
53 Outside air temperature Displays the value of an external outside temperature sensor.
X X X
69 Outside humidity
Displays the value of an external outside humidity sensor.
X X X
70 Room humidity
Displays the value of an external room humidity sensor.
X
X
73 Room CO
2
concentration
Displays the value of an external room CO
2
sensor.
X
X
When the absolute setpoint is displayed, only the heating setpoint is shown on the
display.
Note